The I/O bus view displays an overview of all data points and allows you to log the test results.
Icon | Description |
---|---|
Test passed | |
Test failed | |
Test is not yet checked |
- In the Status Bar, click the Save Device button to ensure all objects have been saved.
- Click a line item to display the data point test options.
- Select the applicable test result from the drop-down list, (Failed or Passed).
- Do one of the following:
- If the result is Failed, select a reason from the Comment drop-down list, and complete the Tested by and Assigned to fields.
- If the result is Passed, complete the Tested by field.
- Click
to save your changes and collapse the row, or click
to cancel.
NOTE: Saved results are logged as new entries in the Commissioning history event log.