Up to two exhaust fans can be connected to the Economizer Controller.

If Exhaust Fan 1 is connected and configured, Exhaust Fan 1 parameter group (L, M and H) is available depending on fan configuration.

If Exhaust Fan 2 is connected and configured, Exhaust Fan 2 parameter group (L, M and H) is available depending on fan configuration.

The controller energizes Exhaust Fan Relay 1 and Exhaust Fan Relay 2 if the damper position reaches Exhaust Fan 1 parameter setting and Exhaust Fan Relay 2 parameter setting respectively. The selection of L, M or H matches the current fan speed (1FAN SPD LV).

Note that if terminal ACT-FB is configured, the damper position is the damper feedback position. If feedback signal is unavailable, it is the simulated position.

Different Exhaust Fan Setpoints with Different Configured Outputs

 

1-stage Cooling2)

2-stage Cooling2)

3-stage Cooling2)

1-speed Fan1)

EX H3) (regardless of cooling demand)

EX H3) (regardless of cooling demand)

EX H3) (regardless of cooling demand)

2-speed Fan1)

EX L4) (0 or 1 cooling demand)

EX H3) (2 cooling demands)

EX L4) (0 or 1 cooling demand)

EX H3) (2 cooling demands)

EX L4) (0 or 1 cooling demand)

EX H3) (2 or 3 cooling demands)

3-speed Fan1)

EX L4) (0 or 1 cooling demand)

EX H3) (2 cooling demands)

EX L4) (0 or 1 cooling demand)

EX H3) (2 cooling demands)

EX L4) (0 or 1 cooling demand)

EX M5) (2 cooling demands)

EX H3) (3 cooling demands)

1

Configured by '6FAN'.

4

EX L = Exhaust Fan 1/2 low-speed parameter setting

2

Configured by Y1O, Y2O or Y3O.

5

EX M = Exhaust Fan 1/2 medium-speed parameter setting

3

EX H = Exhaust Fan 1/2 high-speed parameter setting