Parameter | Description |
---|---|
7DAMPER MIN POS | Press Enter to test if the Economizer Controller can drive damper to minimum position. |
7DAMPER CLOSE | Press Enter to test if the Economizer Controller can drive damper to 100% Closed. |
7DAMPER OPEN | Press Enter to test if the Economizer Controller can drive damper to 100% Open. |
7DAMPER ALL | Press Enter to perform all the above tests and then drive damper to 100% Closed. |
7DAMPER | Press Enter to test if the Economizer Controller can drive damper to the selected voltage. |
7Y1O | Press Enter to test if the Economizer Controller can turn on or off the first stage of cooling (close or open relay Y1O). |
7Y2O | Press Enter to test if the Economizer Controller can turn on or off the second stage of cooling (close or open relay Y2O). |
7AUX1-O | Press Enter to test AUX1-O connection (close or open relay AUX1-O). |
7AUX2-O | Press Enter to test AUX2-O connection (close or open relay AUX2-O). |
7AUX AO | Press Enter to test if the Economizer Controller can set the AUX AO (VFD0-10) to the selected voltage. |