Parameter | Description | Value | Default |
---|---|---|---|
6OCC | Configures if occupancy status receives signal from the connected thermostat or is displayed as 'ALWAYS' in the Economizer Controller. | T-STAT ALWAYS | T-STAT |
6AUX1-I | Auxiliary DI-1. Configurable as:
| NONE SHUTDWN PREOCC HP(B) HP(O) W1 Y3 IN | W1 |
6AUX2-I | Auxiliary DI-2. Configurable as:
Note: Whichever is chosen for '6AUX1-I' doesn't appear in the list of '6AUX2-I'. | NONE SHUTDWN PREOCC HP(B) HP(O) W1 Y3 IN | NONE |
6OAT SIG | Configures signal type of OAT sensor. | NTC10K 0-10V | NTC10K |
6RAT SIG | Configures signal type of RAT sensor. | NONE 0-10V NTC10K | NONE |
6OAH SIG | Configures signal type of OAH sensor. | 0-10V NONE 4-20mA | NONE |
6RAH SIG | Configures signal type of RAH sensor. | ||
6MAT SIG | Configures signal type of MAT or LAT sensor. | NTC10K 0-10V | NTC10K |
6AUX-AI1 | Auxiliary AI-1. Configurable as:
| NONE PRESSURE CO2 | NONE |
6X-AI1 SIG | Configures CO2 sensor type. Dynamic item. Appears only if 'CO2' is selected for '6AUX-AI1'. | 0-10V 2-10V 0-5V | 0-10V |
6CO2 Rng L | Configures the low limit of CO2 measuring range. Dynamic item. Appears only if 'CO2' is selected for '6AUX-AI1'. | 0...500; increment by 10 | 0 |
6C02 Rng H | Configures the high limit of CO2 measuring range. Dynamic item. Appears only if 'CO2' is selected for '6AUX-AI1'. | 1000...3000; increment by 50 | 2000 |
6AUX-AI2 | Choose 'ACT FB' if feedback signal is available from the connected damper actuator. Otherwise, choose 'NONE'. | ACT FB NONE | ACT FB |
6AUX-AO | Choose 'VFD' if a VFD (Variable Frequency Drive) is connected to the Economizer. Otherwise, choose 'NONE'. | NONE VFD | NONE |
6Y2O | Choose 'COOL 2' if Cooling Stage 2 is available (another compressor is connected to the Economizer). Otherwise, choose 'NONE'. | COOL 2 NONE | COOL 2 |
6AUX1-O | Auxiliary DO-1. Configurable as:
| NONE ERV ALARM SUP FAN EXHAUST Y3O | EXHAUST |
6AUX2-O | Auxiliary DO-2. Configurable as:
Note: Of all but Exhaust Fan, whichever is chosen for '6AUX1-O' doesn't appear in the list of '6AUX2-O'. | NONE ERV ALARM SUP FAN EXHAUST Y3O | ALARM |
6FAN | Configures fan speeds of the variable speed supply fan. | 1SPEED 2SPEED 3SPEED VFD FAN | 2SPEED |
6RS485 | Switch between MSTP and Modbus slave. | MSTP MODBUSSLV | MSTP |