Intelligent Valve as a dynamic control valve is part of an HVAC control application on an automation station [N1]. The automation station [N1] sends a setpoint 0…100 % to the Intelligent Valve based on demand. This is done in analog form (0…100 % = DC 0…10 V) or remotely via BACnet IP.
Intelligent Valve follows this setpoint and sets the appropriate volume flow, e.g. in volume flow control mode. The following example depicts this based on a pre-control circuit.
The factory setting for the Intelligent Valve application is 2-port; for EXG../EXF.., the object VlvDsgn (Valve design) must be changed to "3-port" in ABT Go or ABT Site.
2-port valves | 3-port valves | |||
|---|---|---|---|---|
|
| ||||
N1 | Automation station | |||
T | Temperature sensor in the comfort control circuit | |||
B7 | Return temperature sensor (part of the Intelligent Valve) | |||
B26 | Flow temperature sensor (part of the Intelligent Valve) | |||