The tables below contain the available commands for all data points. The commands that are available for a data point are determined by the element category and the SiB-X file of the FS20. The commands available for setting the mode within the management system are read from the SiB-X file. The file ois_dp-<unit_name>-vusis.xml (for example ois_dp-FS20-vualoxerv.xml for FS20) contains the OIS data point list.
The following entry defines, for example, that the commands ON and OFF are available:
<Attribute name="accepted_modes_name_list" type="s" value="['on', 'off']" />.
Most of the commands are effective only in the appropriate context.
Commands for Setting the Mode
Command (Key Word) | Command Number | Command Name |
---|---|---|
OFF | 11 | Switch off |
ON | 12 | Switch on |
MANNED | 13 | Manned |
UNMANNED | 14 | Unmanned |
FAST | 20 | Equipment Test |
SLOW | 21 | Renovation |
TEST | 22 | Detector Test |
TEST_RT | 22 | Controls Test |
DEFAULT | 43 | End Test |
ISA_ACTIVATED | 25 | Activate |
ISA_DEACTIVATED | 35 | Deactivate |
ISA_OFF_TEMP | 15 | Temporary Switch off |
ISA_OFF_EXTERNAL | 16 | External Switch off |
ISA_OFF_ALARM_EVALUATION | 17 | Alarm Evaluation off |
ISA_OFF_TAMPER_EVALUATION | 18 | Tamper Evaluation off |
ISA_ACTIVATED_ALERT | 26 | Activate_Alert |
ISA_ACTIVATED_EVAC | 27 | Activate_Evacuation |
ISA_ACTIVATED_PRIMARY | 28 | Activate_Primary |
ISA_ACTIVATED_SECONDARY | 29 | Activate_Secondary |
ISA_ACTIVATED_INDICATION | 30 | Activate Alarm Indicator |
ISA_ACTIVATED_TEMPORARY | 31 | Temporary Activation |
ISA_OFF_MANUAL | 47 | manual Alarm off |
ISA_OFF_NON_MANUAL | 48 | automatic Alarm off |
ISA_OFF_CONTROLS | 49 | Control off |
ISA_OFF_CONTROLS_RT | 57 | Control off |
ISA_OFF_NOTIFICATION_APPLIANCES | 50 | Sounder off |
ISA_ON_MANUAL | 51 | manual Alarm on |
ISA_ON_NON_MANUAL | 52 | automatic Alarm on |
ISA_ON_CONTROLS | 53 | controls on |
ISA_ON_CONTROLS_RT | 58 | controls on |
ISA_ON_NOTIFICATION_APPLIANCES | 54 | Sounder on |
ISA_TEST_MANUAL | 55 | Test manual Alarm |
ISA_TEST_NON_MANUAL | 56 | Test automatic Alarm |
DISABLED | 60 | Switch off |
AUTOMATIC_RELEASE_DISABLED | 61 | Automatic Extinguishing off |
ENABLED | 62 | Switch on |
ISA_WALKTEST | 63 | Walk test |
ISA_WALKTEST_MANUAL | 64 | MCP zones walk test |
ISA_WALKTEST_NON_MANUAL | 65 | Non-MCP zones walk test |
ISA_CTRL_AUTOMATIC | 66 | Automatic Control |
ISA_CTRL_MANUAL | 67 | Manual Control |
START_INVESTIGATION_TIME | 273 | Start Investigation-Time |
STOP_INVESTIGATION_TIME | 274 | Stop Investigation-Time |
Additional Commands
Command (Key Word) | Command Number | Command Name |
---|---|---|
TIME_SYNC | 70 | Clock-time Synchronisation |
RESET_STATION | 97 | RESET Station |
RESET_GROUP | 96 | RESET Group |
RESET_SYSTEM | 98 | RESET System |
ACKNOWLEDGE_STATION | 95 | ACKNOWLEDGE Station |
ISA_ACTIVATED_VOICE_EVAC_EMERGENCY | 76 | Evac Voice - EVAC EMERGENCY |
ISA_ACTIVATED_VOICE_EVAC_FIRE | 77 | Evac Voice - EVAC FIRE |
ISA_ACTIVATED_VOICE_ALERT | 78 | Evac Voice - ALERT |
ISA_ACTIVATED_VOICE_TEST_ESCALATION | 79 | Voice Test Escalation |
ISA_ACTIVATED_VOICE_CUSTOM1 | 80 | Evac Voice Custom 1 |
ISA_ACTIVATED_VOICE_CUSTOM2 | 81 | Evac Voice Custom 2 |
ISA_ACTIVATED_VOICE_SCHOOLBELL | 82 | Evac Voice School bell |
ISA_ACTIVATED_VOICE_TEST | 83 | Evac Voice - TEST |
ISA_ACTIVATED_VOICE_CLEAR | 84 | Evac Voice - ALL CLEAR |
Commands for BACNET_BLOCK_CMD Object
The commands BLK_CMD_ACK_EXCEPT_AREAS, BLK_CMD_RESET_EXCEPT_AREAS, and BLK_CMD_SILENCE_BUZZER are not available with the BACnetCommandAreaElem type block command object. With the BACnetCommandPanelElem block command object, all commands are available. These BACnet data points are currently not used.
Command (Key Word) | Command Number | Command Name |
---|---|---|
BLK_CMD_ACK_ALL | 100 | ACKNOWLEDGE Station |
BLK_CMD_RESET_ALL | 101 | RESET Station |
BLK_CMD_SILENCE_ALL | 102 | Silence all |
BLK_CMD_UNSILENCE_ALL | 103 | Unsilence all |
BLK_CMD_ALARM_DELAY_OFF | 104 | Alarm Delay Off |
BLK_CMD_ACK_EXCEPT_AREAS | 105 | ACKNOWLEDGE without area |
BLK_CMD_RESET_EXCEPT_AREAS | 106 | RESET without area |
BLK_CMD_SILENCE_BUZZER | 107 | Silence Buzzer |
Commands to FS20
The following table gives a brief overview of the FS20 commands supported by Siveillance Control with respect to data points of the fire alarm system:
Siveillance Control Command | Fire Detector | Fire Detector Group/ | Section/ | Area/ | AVC | Fire Brigade Key Depot | Fire Control Panel |
---|---|---|---|---|---|---|---|
Acoustics Off | X | X |
|
|
|
|
|
Reset | X | X |
|
|
|
| X |
Switch Off | X | X | X | X |
|
|
|
Switch On | X | X | X | X |
|
|
|
Switch Off (Group) | X | X |
|
|
|
|
|
Switch On (Group) | X | X |
|
|
|
|
|
Switch Off Alarming\ |
| X | X | X |
|
|
|
Alarm Verification On\ |
|
|
| X |
|
|
|
Alarm Verification Off\ |
|
|
| X |
|
|
|
Stop Investigation Time |
|
|
|
| X |
|
|
Start Investigation Time |
|
|
|
| X |
|
|
Revision Mode On |
| X |
|
|
|
|
|
Revision Mode Off | X | X |
|
|
|
|
|
Activate Sounders |
|
|
|
|
|
|
|
Activate EVAC |
|
|
|
|
|
|
|
Activate Alert |
|
|
|
|
|
|
|
Activate Control |
|
|
|
|
|
|
|
Deactivate |
|
|
|
|
|
|
|
Release |
|
|
|
|
| X |
|
Siveillance Control Command | Fire Evacuation Group/ | UniversalEVAC Parent and Child/ | 2-Phase EVAC, Parent and Child/ | Fire Control Group (Fire Zone) | Fire Control Unit, Parent and Child Hierarchy | Fire Transmission Unit Parent Level |
---|---|---|---|---|---|---|
Acoustics Off | X |
|
| X |
|
|
Reset |
|
|
|
|
|
|
Switch Off | X | X | X | X | X | X |
Switch On | X | X | X | X | X | X |
Switch Off (Group) |
|
|
|
|
|
|
Switch On (Group) |
|
|
|
|
|
|
Switch Off Alarming\ |
|
|
|
|
|
|
Alarm Verification On\ |
|
|
|
|
|
|
Alarm Verification Off\ |
|
|
|
|
|
|
Stop Investigation Time |
|
|
|
|
|
|
Start Investigation Time |
|
|
|
|
|
|
Revision Mode On | X | X | X | X | X | X |
Revision Mode Off | X | X | X | X | X | X |
Activate Sounders |
| X |
|
|
|
|
Activate EVAC | X | X | X |
|
|
|
Activate Alert | X |
| X |
|
|
|
Activate Control |
|
|
| X | X | X |
Deactivate | X | X | X | X | X | X |
Release |
|
|
|
|
|
|