The tables below contain the available commands for all data points. The commands that are available for a data point are determined by the element category and the SiB-X file of the FS20. The commands available for setting the mode within the management system are read from the SiB-X file. The file ois_dp-<unit_name>-vusis.xml (for example ois_dp-FS20-vualoxerv.xml for FS20) contains the OIS data point list.

The following entry defines, for example, that the commands ON and OFF are available:

<Attribute name="accepted_modes_name_list" type="s" value="['on', 'off']" />.

Most of the commands are effective only in the appropriate context.

Commands for Setting the Mode

Command (Key Word)

Command Number

Command Name

OFF

11

Switch off

ON

12

Switch on

MANNED

13

Manned

UNMANNED

14

Unmanned

FAST

20

Equipment Test

SLOW

21

Renovation

TEST

22

Detector Test

TEST_RT

22

Controls Test

DEFAULT

43

End Test

ISA_ACTIVATED

25

Activate

ISA_DEACTIVATED

35

Deactivate

ISA_OFF_TEMP

15

Temporary Switch off

ISA_OFF_EXTERNAL

16

External Switch off

ISA_OFF_ALARM_EVALUATION

17

Alarm Evaluation off

ISA_OFF_TAMPER_EVALUATION

18

Tamper Evaluation off

ISA_ACTIVATED_ALERT

26

Activate_Alert

ISA_ACTIVATED_EVAC

27

Activate_Evacuation

ISA_ACTIVATED_PRIMARY

28

Activate_Primary

ISA_ACTIVATED_SECONDARY

29

Activate_Secondary

ISA_ACTIVATED_INDICATION

30

Activate Alarm Indicator

ISA_ACTIVATED_TEMPORARY

31

Temporary Activation

ISA_OFF_MANUAL

47

manual Alarm off

ISA_OFF_NON_MANUAL

48

automatic Alarm off

ISA_OFF_CONTROLS

49

Control off

ISA_OFF_CONTROLS_RT

57

Control off

ISA_OFF_NOTIFICATION_APPLIANCES

50

Sounder off

ISA_ON_MANUAL

51

manual Alarm on

ISA_ON_NON_MANUAL

52

automatic Alarm on

ISA_ON_CONTROLS

53

controls on

ISA_ON_CONTROLS_RT

58

controls on

ISA_ON_NOTIFICATION_APPLIANCES

54

Sounder on

ISA_TEST_MANUAL

55

Test manual Alarm

ISA_TEST_NON_MANUAL

56

Test automatic Alarm

DISABLED

60

Switch off

AUTOMATIC_RELEASE_DISABLED

61

Automatic Extinguishing off

ENABLED

62

Switch on

ISA_WALKTEST

63

Walk test

ISA_WALKTEST_MANUAL

64

MCP zones walk test

ISA_WALKTEST_NON_MANUAL

65

Non-MCP zones walk test

ISA_CTRL_AUTOMATIC

66

Automatic Control

ISA_CTRL_MANUAL

67

Manual Control

START_INVESTIGATION_TIME

273

Start Investigation-Time

STOP_INVESTIGATION_TIME

274

Stop Investigation-Time

Additional Commands

Command (Key Word)

Command Number

Command Name

TIME_SYNC

70

Clock-time Synchronisation

RESET_STATION

97

RESET Station

RESET_GROUP

96

RESET Group

RESET_SYSTEM

98

RESET System

ACKNOWLEDGE_STATION

95

ACKNOWLEDGE Station

ISA_ACTIVATED_VOICE_EVAC_EMERGENCY

76

Evac Voice - EVAC EMERGENCY

ISA_ACTIVATED_VOICE_EVAC_FIRE

77

Evac Voice - EVAC FIRE

ISA_ACTIVATED_VOICE_ALERT

78

Evac Voice - ALERT

ISA_ACTIVATED_VOICE_TEST_ESCALATION

79

Voice Test Escalation

ISA_ACTIVATED_VOICE_CUSTOM1

80

Evac Voice Custom 1

ISA_ACTIVATED_VOICE_CUSTOM2

81

Evac Voice Custom 2

ISA_ACTIVATED_VOICE_SCHOOLBELL

82

Evac Voice School bell

ISA_ACTIVATED_VOICE_TEST

83

Evac Voice - TEST

ISA_ACTIVATED_VOICE_CLEAR

84

Evac Voice - ALL CLEAR

Commands for BACNET_BLOCK_CMD Object

The commands BLK_CMD_ACK_EXCEPT_AREAS, BLK_CMD_RESET_EXCEPT_AREAS, and BLK_CMD_SILENCE_BUZZER are not available with the BACnetCommandAreaElem type block command object. With the BACnetCommandPanelElem block command object, all commands are available. These BACnet data points are currently not used.

Command (Key Word)

Command Number

Command Name

BLK_CMD_ACK_ALL

100

ACKNOWLEDGE Station

BLK_CMD_RESET_ALL

101

RESET Station

BLK_CMD_SILENCE_ALL

102

Silence all

BLK_CMD_UNSILENCE_ALL

103

Unsilence all

BLK_CMD_ALARM_DELAY_OFF

104

Alarm Delay Off

BLK_CMD_ACK_EXCEPT_AREAS

105

ACKNOWLEDGE without area

BLK_CMD_RESET_EXCEPT_AREAS

106

RESET without area

BLK_CMD_SILENCE_BUZZER

107

Silence Buzzer

Commands to FS20

The following table gives a brief overview of the FS20 commands supported by Siveillance Control with respect to data points of the fire alarm system:

Siveillance Control Command

Fire Detector

Fire Detector Group/
Fire Zone

Section/
Fire Zone

Area/
Fire Zone

AVC

Fire Brigade Key Depot

Fire Control Panel

Acoustics Off

X

X

 

 

 

 

 

Reset

X

X

 

 

 

 

X

Switch Off

X

X

X

X

 

 

 

Switch On

X

X

X

X

 

 

 

Switch Off (Group)

X

X

 

 

 

 

 

Switch On (Group)

X

X

 

 

 

 

 

Switch Off Alarming\
Alarm Evaluation Off

 

X

X

X

 

 

 

Alarm Verification On\
Manned Operation

 

 

 

X

 

 

 

Alarm Verification Off\
Unmanned Operation

 

 

 

X

 

 

 

Stop Investigation Time

 

 

 

 

X

 

 

Start Investigation Time

 

 

 

 

X

 

 

Revision Mode On

 

X

 

 

 

 

 

Revision Mode Off

X

X

 

 

 

 

 

Activate Sounders

 

 

 

 

 

 

 

Activate EVAC

 

 

 

 

 

 

 

Activate Alert

 

 

 

 

 

 

 

Activate Control

 

 

 

 

 

 

 

Deactivate

 

 

 

 

 

 

 

Release

 

 

 

 

 

X

 

 

Siveillance Control Command

Fire Evacuation Group/
Fire Zone

UniversalEVAC Parent and Child/
Fire Evacuation Alarm Device

2-Phase EVAC, Parent and Child/
Fire Evacuation Alarm Device

Fire Control Group (Fire Zone)

Fire Control Unit, Parent and Child Hierarchy

Fire Transmission Unit Parent Level

Acoustics Off

X

 

 

X

 

 

Reset

 

 

 

 

 

 

Switch Off

X

X

X

X

X

X

Switch On

X

X

X

X

X

X

Switch Off (Group)

 

 

 

 

 

 

Switch On (Group)

 

 

 

 

 

 

Switch Off Alarming\
Alarm Evaluation Off

 

 

 

 

 

 

Alarm Verification On\
Manned Operation

 

 

 

 

 

 

Alarm Verification Off\
Unmanned Operation

 

 

 

 

 

 

Stop Investigation Time

 

 

 

 

 

 

Start Investigation Time

 

 

 

 

 

 

Revision Mode On

X

X

X

X

X

X

Revision Mode Off

X

X

X

X

X

X

Activate Sounders

 

X

 

 

 

 

Activate EVAC

X

X

X

 

 

 

Activate Alert

X

 

X

 

 

 

Activate Control

 

 

 

X

X

X

Deactivate

X

X

X

X

X

X

Release