The following table gives a brief description of the SIPORT door commands supported by Siveillance Control.

OIS SIPORT Door Commands

Siveillance Control Command

SIPORT Actions

Description

Lock Permanently

Door Lock + Block Reader

The Siveillance Control door command Lock Permanently performs the SIPORT actions Door lock and Block Reader by setting the SIPORT reader attributes FO (Forced Open)to 0 and SP (Block Reader)to 4.

Unlock Permanently

Door Unlock + Unblock Reader

The Siveillance Control door command Unlock Permanently performs the SIPORT actions Unlock Door and Unblock Reader by setting the SIPORT reader attributes F0 to 1 and SP to 0.

Unlock Temporary

Opening Procedure

The Siveillance Control door command Unlock Temporary performs the SIPORT action Opening Procedure to the door by setting the SIPORT reader attributes OP (Opening Procedure) to 1; provided if the I2 attribute in SIPORT is to set to 1.

Secure

Door Lock +Unblock Reader

The Siveillance Control door command Secure performs the SIPORT action Door Lock by setting the SIPORT reader attribute FO to 0 and SP to 0.

Reset

 

Resets door message in Siveillance Control.

 

OIS SIPORT Input Commands

The following table gives a brief description of the SIPORT input commands supported by Siveillance Control.

OIS SIPORT Input Commands

Siveillance Control Command

SIPORT Actions

Description

Switch on

Enable Alarm

The Siveillance Control Switch on command enables the SIPORT input point by setting the attribute EN to 1.

Switch off

Disable Alarm

The Siveillance Control Switch off command disables the SIPORT input alarm by setting the attribute EN to 0.

 

OIS SIPORT Output Commands

The following table gives a brief description of the SIPORT output commands supported by Siveillance Control.

OIS SIPORT Output Commands

Siveillance Control Command

SIPORT Actions

Description

Start

switch on relay

The Siveillance Control Start command performs the SIPORT action switch on relay by setting the attribute CV to 1.

Stop

switch off relay

The Siveillance Control Stop command performs the SIPORT action switch off relay by setting the attribute CV to 0.

NOTICE

Refer to the SIPORT kernel document EW3K32P.pdf for more information about the attributes.