1. From the Launch menu, select DB Builder.
  1. Navigate to Connectors → BACnet.
  1. Select the BACnet connector from which the schedule originates.
  1. Discover the points to find the schedule object .
  1. Under an equip, import the BACnet schedule into the database.
  1. One at a time, select each schedule point in DB Builder and go the gear icon at the bottom left to open the tools list.
  1. From the tools list, find and select the BACnet ScheduIe Configuration tool.
  • A popup menu displays:

The tool popup presents the following options:

  • Schedule: This dropdown lists all the available schedules within FIN that correspond to the type the user is seeking, from which they can make a selection.
  • Automatic Schedule Sync—reading: The user can enable/disable reading—syncing schedule events from an endpoint BACnet schedule back to a centralized FIN schedule.
  • The read syncing supports the following:
  • Weekly_Schedule: This property will be synced after the BACnet schedule weekly part updates and poll frequency is met.
    Exception_Schedule: This property will be synced after the BACnet schedule exception part updates and poll frequency is met.
  • Schedule_Default:This property will be synced after the BACnet schedule default value updates and poll frequency is met.
  • Automatic Schedule Sync—writing: The user can choose whether to enable disable syncing schedule events from a centralized FIN schedule to endpoint BACnet schedules.
  • The write syncing supports the following:
  • Weekly_Schedule: This property will be written when the FIN schedule weekly part updates.
  • Exception_Schedule: This property will be written when the FIN schedule event part updates.
  • Schedule_Default: This property will be written when the FIN schedule default value is set.