The "License error - over point capacity limit" error indicates that the projects within the server contain more points (points without the 'aux' marker tag) than the license is set to allow. To resolve this error, there are few options. First is to remove our demo project if it exists. The second option is to delete points to get under the limit. The third option is to make some of the non aux points as auxPoints if auxPoint limit available. Our demo contains about 1,190 points. Depending on your license, it may be enough or you would have to remove more from your project(s). The user can follow the below steps for either option they want to go with.
Option 1:
Remove the demo project that comes with the installation if not yet removed. Read the "Removing Demo Project" section on how to do this.
Option 2:
Go to DB Builder of project
Select the "points" tab
Filter for the points you wish to remove
Once selected, click on the trash icon and move them to the trash
Restart the Desigo Optic service
NOTE: If the user wants to restore some points if they deleted too many, or have upgraded their license, or they want to convert some to auxPoints, they can look at the "Restoring items from trash" section.
Option 3:
- Go to DB Builder of project
- Select the "points" tab
- In the "marker" tag column open the filter menu and select 'aux' from the list. Press "ok" to filter the results.
- Then select points that are not aux points
- Once selected, the user can select the trend icon top right corner to convert them to aux points
- Now the user has moved some points from the points pool to the auxPoints pool if available.
- Restart the Desigo Optic service