The "License error - over auxPoint capacity limit" error indicates that the projects within the server contain more auxPoints (points tagged with the 'aux' marker tag) than the license is set to allow. To resolve this error, there are few options. First is to remove our demo project if it exists. The second option is to delete some auxPoints to get under the limit. The third option is to remove aux marker tag to make them non auxPoints if points limit is available. Our demo contains 30 if you decide to keep it. Depending on your license, it may be enough or you would have to remove more from your project(s). The user can follow the below steps for either option they want to go with.

Option 1:

Remove the demo project that comes with the installation if not yet removed. Read the "Removing Demo Project" section on how to do this.

Option 2:

  1. Go to DB Builder of project
  1. Select the "points" tab
  1. In the "marker" tag column open the filter menu and select 'aux' from the list. Press "ok" to filter the results.
  1. Adjust the amount of results shown on the page based on how many auxPoints you need to view/edit at once.
  1. Click on the trash icon and move them to the trash
  1. Restart the Desigo Optic service.


NOTICE! If the user wants to restore some auxPoints if they deleted too many or have upgraded their license, they can look at the "Restoring items from trash" section.

Option 3:

  1. The user would follow option 2
  1. Then convert some to non aux points by removing the 'aux' marker tag from the selected points
  1. Go to folio and click on the trash icon top right corner to view trash
  1. Select points to convert to non aux points
  1. Edit them to remove the 'aux' marker tag and apply
  • Now the user has moved some points from the auxPoints pool to the points pool if available.