Before migrating your subscription between partitions, you must back up your device data.

  1. First, take a snapshot of your project: Snapshot
  1. Next, save your license file locally.
  1. Backup any Modbus register maps
  1. Note the users and groups inside Optic Viewing, editing, and deleting users Access Groups.
  1. Backup your device settings. Navigate to the F200s gateway page and note the following information for restoration later:
  • Activation code. Navigate to Configuration UI > Operation tab.
  • Device IP address. F200 gateway > Network tab > IP settings
  • Device settings. Navigate to Maintenance tab > Device Settings section.
  1. Update F200 to the Latest Operating System Version.
  1. Finally, update Desigo Optic.