Procedural Overview
Cloud Connector is required to create a connection between Desigo Optic (DO) and Building X (BX). To finalize this connection, you must register your server on the Building X side and install the Desigo Optic server on Building X with the appropriate distribution assigned. Finally, you will initialize synchronization and proceed to the Desigo Optic Tools User Guide to set up bidirectional data synchronization with tagged points.
Procedure Steps
The following steps are required to configure Cloud Connector.
Registering a server with Building X
- Use the following link to open Devices in the Building X cloud: https://assets.bpcloudapps.siemens.com/#/login
- Select Sites.
- Select or add a site or building from the All sites or All Buildings list where you would like to add your device.
- Select + Add.
- Enter the activation key you saved in the Activation key field.
- Select Validate.
- Additional fields will display.
- Enter a name in the Custom name field. Other fields are not required.
- Select Add.
- Your device has been added to Building X. The Assign distribution dialog opens.
- The first addition of a device will prompt the assign distribution dialogue.
- Select Desigo Optic as the distribution type.
- Select the distribution version matching the version number of your DO install.
- Select Save.
- After loading finishes, you will see a message in the bottom right corner announcing your Desigo Optic distribution has been assigned to the selected device on the Building X side. The device will appear under applications.
- From the Applications tab, checkmark the box alongside your application and select Synchronize.
- The Desigo Optic Cloud Connector app installs.
- Check the device connection state in the Information tab.
- From Desigo Optic > the BuildingX app, ensure the websocket connection status says "Connected".
- You have completed the connection between Building X and Desigo Optic. Cloud Connector is configured and may be used to synchronize specific data points.