This section provides an overview the procedure to migrate between any two consecutive Desigo Optic 5.1.X versions, i.e. 5.1.7 to 5.1.9. Migration covers the following tag changes:

Old tag

Changed tag

weather

weatherStation

weatherRef

weatherStationRef

job

Now a marker tag

jobExpr

New tag that contains the job function

schedule

Now a marker tag

scheduleGrid

New tag that contains the schedule events

 

NOTICE! If tags did not update, run the finMigrateProject() function in the Folio app to update them.

 

When downgrading a Desigo Optic F200 device from version 5.1.9 to an earlier version, you will need to reload your signed certificate(s) for the HTTPS proxy server. This requirement applies if you are using a new or cleared F200 device that had 5.1.9 as the first installation of Desigo Optic, unless you are using the Desigo Optic self-signed certificate.

Failure to do so will result in loss of access to Desigo Optic and misleading device connection status.