Testing a solenoid actuator
- Remove the elbow connector and M12 8-pole connector from the solenoid actuator.
- Depending on the test, plug the relevant connector to the test device.
- Perform the requested test.
- After completing the test, plug the elbow connector and the M12 8-pole connector back on the actuator.
Risk of box overheating
To prevent the tool from overheating, the maximum on-time for simulating the actuation of the actuator should be less than one minute.
Testing the pressure switch
- Remove the elbow connector from the pressure switch.
- Plug the connector to the test device.
- Perform the requested test.
- After completing the test, plug the elbow connector back onto the pressure switch.
For more details, refer to the mounting and installation documentation.