Main module | Extension module | Main module |
Item | Description | Main module | Extension module | Main module |
|---|---|---|---|---|
|
| Quantity | Quantity | Quantity |
1 | Upper cross member | 1 | 1 | 1 |
2 | Intermediate support | 1 | 1 | - |
3 | Upright | 2 | 1 | 2 |
4 | Cross member | 2 | 2 | 2 |
5 | Right strut | 1 | - | 1 |
6 | Left strut | 1 | - | 1 |
7 | Extension strut | - | 1 | - |
8 | Pipe clamp ∅ 1/2ʺ | - | - | 2 |
9 | Pipe clamp ∅ 3/4ʺ | - | - | 1 |
10 | Pipe clamp ∅ 55 mm | - | - | 1 |
Type of modules
Module number | Product code | Reference |
|---|---|---|
1 | S54476-B610-A1 | RACF-140L-1 – Main module for free-standing rack (1 cylinder) |
2 | S54476-B610-A2 | RACF-140L-2 – Main module for free-standing rack (2 cylinders) |
3 | S54476-B610-A3 | RACF-140L-3 – Main module for free-standing rack (3 cylinders) |
4 | S54476-B610-A4 | RACF-140L-4 – Main module for free-standing rack (4 cylinders) |
5 | S54476-B610-A5 | RACF-140L-5 – Main module for free-standing rack (5 cylinders) |
4* | S54476-B611-A4 | RACF-140L-EX4 – Extension module for free-standing rack (4 cylinders) |
5* | S54476-B611-A5 | RACF-140L-EX5 – Extension module for free-standing rack (5 cylinders) |
List of modules for a 1-row arrangement (1 to 15 cylinders)
| Required space for installation (including cylinders) | |||||
Number of cylinders on 1 row | Required module number | Number of threaded rods - 1 row (S54476-B618-A1) | Number of cylinder clamps (S54476-B617-A1) | Number of DN50 (S54476-B609-A1) or DN80 (S54476-B609-A2) manifold clamps | Length (mm) | Width (mm) |
1 | 1 | 2 | 1 | - | 653 | 402 |
2 | 2 | 3 | 2 | 2 | 1 026 | 402 |
3 | 3 | 4 | 3 | 2 | 1 400 | 402 |
4 | 4 | 5 | 4 | 3 | 1 772 | 402 |
5 | 5 | 6 | 5 | 3 | 2 145 | 402 |
6 | 2+4* | 7 | 6 | 5 | 2 638 | 402 |
7 | 3+4* | 8 | 7 | 5 | 3 012 | 402 |
8 | 4+4* | 9 | 8 | 6 | 3 384 | 402 |
9 | 5+4* | 10 | 9 | 6 | 3 757 | 402 |
10 | 5+5* | 11 | 10 | 6 | 4 130 | 402 |
11 | 3+4*+4* | 12 | 11 | 8 | 4 624 | 402 |
12 | 4+4*+4* | 13 | 12 | 9 | 4 996 | 402 |
13 | 5+4*+4* | 14 | 13 | 9 | 5 369 | 402 |
14 | 5+4*+5* | 15 | 14 | 9 | 5 742 | 402 |
15 | 5+5*+5* | 16 | 15 | 9 | 6 115 | 402 |
List of modules for a 2-row arrangement (3 to 30 cylinders)
| Required space for installation (including cylinders) | |||||
Number of cylinders on 2 rows | Required module number | Number of threaded rods - 2 rows (S54476-B618-A2) | Number of cylinder clamps (S54476-B617-A1) | Number of DN50 (S54476-B609-A1) or DN80 (S54476-B609-A2) manifold clamps | Length | Width |
3 / 4 | 2 | 3 | 2 | 2 | 1 026 | 762 |
5 / 6 | 3 | 4 | 3 | 2 | 1 400 | 762 |
7 / 8 | 4 | 5 | 4 | 3 | 1 772 | 762 |
9 / 10 | 5 | 6 | 5 | 3 | 2 145 | 762 |
11 / 12 | 2+4* | 7 | 6 | 5 | 2 638 | 762 |
13 / 14 | 3+4* | 8 | 7 | 5 | 3 012 | 762 |
15 / 16 | 4+4* | 9 | 8 | 6 | 3 384 | 762 |
17 / 18 | 5+4* | 10 | 9 | 6 | 3 757 | 762 |
19 / 20 | 5+5* | 11 | 10 | 6 | 4 130 | 762 |
21 / 22 | 3+4*+4* | 12 | 11 | 8 | 4 624 | 762 |
23 / 24 | 4+4*+4* | 13 | 12 | 9 | 4 996 | 762 |
25 / 26 | 5+4*+4* | 14 | 13 | 9 | 5 369 | 762 |
27 / 28 | 5+4*+5* | 15 | 14 | 9 | 5 742 | 762 |
29 / 30 | 5+5*+5* | 16 | 15 | 9 | 6 115 | 762 |
Example of a 2-row arrangement with 10 cylinders
4-row arrangement
In a 4-row arrangement, the racks consist of two pairs of double rows of cylinders, fixed back to back.
The manifolds are located slightly higher than in a 1- or 2-row arrangement since they are mounted on rails (Connector 4r - S54476-B604-A1) attached to the upper cross members.