Object type | Supported | Can be created dynamically | Can be deleted dynamically |
Analog Input | 🗷 | 🞎 | 🞎 |
Analog Output | 🗷 | 🞎 | 🞎 |
Analog Value | 🗷 | 🞎 | 🞎 |
Averaging | 🞎 | 🞎 | 🞎 |
Binary Input | 🗷 | 🞎 | 🞎 |
Binary Output | 🗷 | 🞎 | 🞎 |
Binary Value | 🗷 | 🞎 | 🞎 |
Calendar | 🞎 | 🞎 | 🞎 |
Command | 🞎 | 🞎 | 🞎 |
Device | 🗷 | 🞎 | 🞎 |
Event Enrollment | 🞎 | 🞎 | 🞎 |
File | 🞎 | 🞎 | 🞎 |
Group | 🞎 | 🞎 | 🞎 |
Life-Safety-Point | 🞎 | 🞎 | 🞎 |
Life-Safety-Zone | 🞎 | 🞎 | 🞎 |
Loop | 🞎 | 🞎 | 🞎 |
Multi-State Input | 🞎 | 🞎 | 🞎 |
Multi-State Output | 🞎 | 🞎 | 🞎 |
Multi-State Value | 🗷 | 🞎 | 🞎 |
Notification Class | 🞎 | 🞎 | 🞎 |
Program | 🞎 | 🞎 | 🞎 |
Pulse-Converter | 🞎 | 🞎 | 🞎 |
Schedule | 🗷 | 🞎 | 🞎 |
Trend Log | 🞎 | 🞎 | 🞎 |
Access Door | 🞎 | 🞎 | 🞎 |
Event Log | 🞎 | 🞎 | 🞎 |
Load Control | 🞎 | 🞎 | 🞎 |
Structured-View | 🗷 | 🞎 | 🞎 |
Trend Log Multiple | 🞎 | 🞎 | 🞎 |
Access Point | 🞎 | 🞎 | 🞎 |
Access Zone | 🞎 | 🞎 | 🞎 |
Access User | 🞎 | 🞎 | 🞎 |
Access Rights | 🞎 | 🞎 | 🞎 |
Access Credential | 🞎 | 🞎 | 🞎 |
Credential Data Input | 🞎 | 🞎 | 🞎 |
Characterstring Value | 🞎 | 🞎 | 🞎 |
Datetime Value | 🞎 | 🞎 | 🞎 |
Large Analog Value | 🞎 | 🞎 | 🞎 |
Bitstring Value | 🞎 | 🞎 | 🞎 |
Octetstring Value | 🞎 | 🞎 | 🞎 |
Time Value | 🞎 | 🞎 | 🞎 |
Integer Value | 🞎 | 🞎 | 🞎 |
Positive Integer Value | 🗷 | 🞎 | 🞎 |
Object type | Supported | Can be created dynamically | Can be deleted dynamically |
Date Value | 🞎 | 🞎 | 🞎 |
Datetime Pattern Value | 🞎 | 🞎 | 🞎 |
Time Pattern Value | 🞎 | 🞎 | 🞎 |
Date Pattern Value | 🞎 | 🞎 | 🞎 |
Network Security | 🞎 | 🞎 | 🞎 |
Global Group | 🞎 | 🞎 | 🞎 |
Notification Forwarder | 🞎 | 🞎 | 🞎 |
Alert Enrollment | 🞎 | 🞎 | 🞎 |
Channel | 🞎 | 🞎 | 🞎 |
Lighting Output | 🞎 | 🞎 | 🞎 |
Binary Lighting Output | 🞎 | 🞎 | 🞎 |
Network Port | 🞎 | 🞎 | 🞎 |
Timer | 🞎 | 🞎 | 🞎 |
Elevator Group | 🞎 | 🞎 | 🞎 |
Lift | 🞎 | 🞎 | 🞎 |
Escalator | 🞎 | 🞎 | 🞎 |
Accumulator | 🞎 | 🞎 | 🞎 |
Properties | supported | Readable/ Writable |
Range restrictions |
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Present_Value | 🗷 | R | |
Description | 🗷 | W | |
Device_Type | 🗷 | R | |
Status_Flags | 🗷 | R | |
Event_State | 🗷 | R | |
Reliability | 🗷 | R | |
Out_Of_Service | 🗷 | W | |
Units | 🗷 | W | |
Min_Pres_Value | 🗷 | W | |
Max_Pres_Value | 🗷 | W | |
Resolution | 🗷 | W | |
COV_Increment | 🗷 | W | |
Property_List | 🗷 | R | |
Profile_Name | 🗷 | R |
Analog Input
Properties | supported | Readable/ Writable |
Range restrictions |
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Present_Value | 🗷 | W | |
Description | 🗷 | W | |
Device_Type | 🗷 | R | |
Status_Flags | 🗷 | R | |
Event_State | 🗷 | R | |
Reliability | 🗷 | R | |
Out_Of_Service | 🗷 | W | |
Units | 🗷 | W | |
Min_Pres_Value | 🗷 | W | |
Max_Pres_Value | 🗷 | W | |
Resolution | 🗷 | W | |
Priority_Array | 🗷 | R | |
Relinquish_Default | 🗷 | W | |
COV_Increment | 🗷 | W | |
Property_List | 🗷 | R | |
Profile_Name | 🗷 | R |
Analog Output
Analog Value
Properties | supported | Readable/ Writable |
Range restrictions |
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Present_Value | 🗷 | R | |
Description | 🗷 | W | |
Status_Flags | 🗷 | R | |
Event_State | 🗷 | R | |
Reliability | 🗷 | R | |
Out_Of_Service | 🗷 | W | |
Units | 🗷 | W | |
Priority_Array | 🗷 | R | |
Relinquish_Default | 🗷 | W | |
COV_Increment | 🗷 | W | |
Min_Pres_Value | 🗷 | W | |
Max_Pres_Value | 🗷 | W | |
Resolution | 🗷 | W | |
Property_List | 🗷 | R | |
Profile_Name | 🗷 | R |
Binary Input
Properties | supported | Readable/ Writable |
Range restrictions |
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Present_Value | 🗷 | R | |
Description | 🗷 | W | |
Device_Type | 🗷 | R | |
Status_Flags | 🗷 | R | |
Event_State | 🗷 | R | |
Reliability | 🗷 | R | |
Out_Of_Service | 🗷 | W | |
Polarity | 🗷 | W | |
Inactive_Text | 🗷 | R | |
Active_Text | 🗷 | R | |
Property_List | 🗷 | R | |
Profile_Name | 🗷 | R |
Binary Output
Properties | supported | Readable/ Writable |
Range restrictions |
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Present_Value | 🗷 | W | |
Description | 🗷 | R | |
Device_Type | 🗷 | R | |
Status_Flags | 🗷 | R | |
Event_State | 🗷 | R | |
Reliability | 🗷 | R | |
Out_Of_Service | 🗷 | W | |
Polarity | 🗷 | W | |
Inactive_Text | 🗷 | R | |
Active_Text | 🗷 | R | |
Minimum_Off_Time | 🗷 | W | |
Minimum_On_Time | 🗷 | W | |
Priority_Array | 🗷 | R | |
Relinquish_Default | 🗷 | W | |
Property_List | 🗷 | R | |
Profile_Name | 🗷 | R |
Binary Value
Properties | supported | Readable/ Writable |
Range restrictions |
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Present_Value | 🗷 | R | |
Description | 🗷 | W | |
Status_Flags | 🗷 | R | |
Event_State | 🗷 | R | |
Reliability | 🗷 | R | |
Out_Of_Service | 🗷 | W | |
Inactive_Text | 🗷 | R | |
Active_Text | 🗷 | R | |
Property_List | 🗷 | R | |
Profile_Name | 🗷 | R |
Device
Properties | supported | Readable/ Writable |
Range restrictions |
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | R | |
Object_Type | 🗷 | R | |
System_Status | 🗷 | R | |
Vendor_Name | 🗷 | R | |
Vendor_Identifier | 🗷 | R | |
Model_Name | 🗷 | R | |
Firmware_Revision | 🗷 | R | |
Application_Software_Version | 🗷 | R | |
Location | 🗷 | W | |
Description | 🗷 | W | |
Protocol_Version | 🗷 | R | |
Protocol_Revision | 🗷 | R | |
Protocol_Services_Supported | 🗷 | R | |
Protocol_Object_Types_Supported | 🗷 | R | |
Object_List | 🗷 | R | |
Structured_Object_List | 🗷 | R | |
Max_APDU_Length_Accepted | 🗷 | R | |
Segmentation_Supported | 🗷 | R | |
Max_Segments_Accepted | 🗷 | R | |
Local_Time | 🗷 | W | |
Local_Date | 🗷 | W | |
UTC_Offset | 🗷 | W | |
Daylight_Savings_Status | 🗷 | R | |
APDU_Segment_Timeout | 🗷 | R | |
APDU_Timeout | 🗷 | R | |
Number_Of_APDU_Retries | 🗷 | R | |
Device_Address_Binding | 🗷 | R | |
Database_Revision | 🗷 | R | |
Active_COV_Subscriptions | 🗷 | R | |
Last_Restart_Reason | 🗷 | R | |
Time_Of_Device_Restart | 🗷 | R | |
Restart_Notification_Recipients | 🗷 | R | |
Serial_Number | 🗷 | R | |
Property_List | 🗷 | R | |
Profile_Name | 🗷 | R |
Multi-state Value
Properties | supported | Readable/ Writable |
Range restrictions |
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Present_Value | 🗷 | R | |
Description | 🗷 | W | |
Status_Flags | 🗷 | R | |
Event_State | 🗷 | R | |
Reliability | 🗷 | R | |
Out_Of_Service | 🗷 | W | |
Number_Of_States | 🗷 | R | |
State_Text | 🗷 | R | |
Property_List | 🗷 | R | |
Profile_Name | 🗷 | R |
Structure View
Object
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Node_Type | 🗷 | R | |
Description | 🗷 | W | |
Subordinate_List | 🗷 | R | |
Profile_Name | 🗷 | R | |
Node_Subtype | 🗷 | R | |
Subordinate_Annotations | 🗷 | R | |
Property_List | 🗷 | R |
Schedule
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Present_Value | 🗷 | W | Writable when out of service |
Description | 🗷 | W | |
Effective_Period | 🗷 | W | |
Weekly_Schedule | 🗷 | W | |
Schedule_Default | 🗷 | W | |
List_Of_Object_Property_References | 🗷 | W | |
Priority_For_Writing | 🗷 | W | |
Status_Flags | 🗷 | R | |
Reliability | 🗷 | W | Writable when out of service |
Out_Of_Service | 🗷 | W | |
Profile_Name | 🗷 | R |
Positive Integer Value
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | 🗷 | R | |
Object_Name | 🗷 | W | |
Object_Type | 🗷 | R | |
Description | 🗷 | W | |
Present_Value | 🗷 | W | |
Profile_Name | 🗷 | R | |
Status_Flags | 🗷 | R | |
Event_State | 🗷 | R | |
Reliability | 🗷 | R | |
Units | 🗷 | W | |
Cov_Increment | 🗷 | W | |
Min_Pres_Value | 🗷 | W | |
Max_Pres_Value | 🗷 | W | |
Out_Of_Service | 🗷 | W | |
Property_List | 🗷 | R |