Voice alarm panel Compact 1000
| PC1002-A3 |
|---|---|
Integrated power supply | |
Manufacturer | Merawex |
Type | ZDSO400-DR2-2U |
Power supply | AC 230 V +10 % / -15 % |
Current consumption | 10 A |
Nominal output voltage | DC 24 V |
Nominal output current | 32 A |
Load capacity of outputs to amplifiers | 6x 30 A |
Battery max charging current | 16 A |
Battery float voltage at 25 °C | 27.1 V |
Battery low charge error voltage | 21 V |
Battery set permissible increase in resistance | 50 mΩ |
Relay outputs | Faults: mains, battery, general |
Relay type | Changeover contacts 1 A @ DC 30 V |
Number of inputs / outputs | |
Analog audio inputs 0 dB (external source) | 4 |
Analog audio inputs 100 V (amplifier) | 4 |
Analog audio outputs 0 dB (to amplifier or external) | 4 |
Speaker lines 100 V | 16 |
Analog control inputs 0...10 V | 8 |
Logic control inputs | 8 Schmitt trigger inputs |
Logic control outputs | 8 electrically isolated relay outputs with changeover contacts |
Fault indicator relay | 1 |
Logic control inputs | |
Input voltage | Low <3 V / High >7 V |
Max. permissible voltage | 36 V |
Input current at 10 V / 12 V / 24 V | ~5 / ‒ / ‒ mA |
Logic control outputs, relays | |
Max. voltage | 48 V |
Max. current | 500 mA per output |
Analog control inputs | |
Measuring range | DC 0…10 V |
Resolution | 8 bit |
Input current at 10 V | ~0.3 mA |
Interfaces | |
Serial interfaces | 1x RS485 9600, 19200, 57600, 115200 Baud |
Ethernet connection | 2x RJ45 (CAT5) 100Base-TX (IEEE 802.3u) |
Audio properties | |
Standard audio output power | 1000 W |
Max. audio output power | 2000 W |
Frequency band | 60 Hz…20 kHz / -1 dB |
Distortion factor | <0.05 % |
Total dynamic range | 103 dB |
Inputs: | Symmetrical Max. amplification freely selectable -20 dB…+60 dB |
| 12 V Optional +24 V or +48 V |
| 6.6 kOhm |
Outputs: | Symmetrical |
| +15 dB |
| 300 Ohm |
Ambient conditions | |
Operating temperature | -5…+40 °C |
Air humidity | 10…90 % rel. |
Dimensions and weights | |
W x H x D mm | 710 x 950 x 305 |
Weight | 55 kg (without batteries) |
Weight for max. configuration | 130 kg (with batteries) |
Protection category and color | |
Protection category (IEC 60529) | IP30 |
Power amplifier (1x500W)
| PV1002-A1 |
|---|---|
Max. audio output power at 100 V | 1x 500 W (Music)1) 1x 350 W (Sinus)2) |
Supply voltage, AC | AC 230 V (85...265 V) |
Supply voltage, DC | DC 24 V (18...30 V) |
Distortion factor at 1 kHz/100 V | <0.2 % |
Frequency band -3 dB | 10 Hz...30 kHz |
Input sensitivity | 1 V at 10 kΩ |
Input impedance at 1 kHz | 10 kΩ |
Unweighted signal-to-noise ratio at 1 kHz | 95 dB |
Signal-to-noise ratio | 102 dB |
Signal inputs | Electronically symmetrical |
Current consumption | |
Efficiency | <91 % |
Standby at DC 24 V | 0.4 A |
Standby at AC 230 V | 0.025 A |
Operation, no signal, all 'Ch' active at DC 24 V | 0.5 A |
Operation, no signal, all 'Ch' active at AC 230 V | 0.038 A |
Full load sine at DC 24 V | 26 A |
Full load sine at AC 230 V | 2.75 A |
Protection | Over-current, overheating |
Operation/fault messages | |
Open collector outputs | AC, DC, Fault, Clip/Temp |
LED at amplifier | - |
LED at adapter board | AC, DC, Fault, Clip/Temp, Operate, Signal |
Remote activation | |
Input amp. ON (optional) | ON: open Off: >5 V @ 680 R Max. DC 24 V |
Connections | |
Signal inputs, operation/fault messages | RJ45 to adapter board |
Power outputs | Plug-in terminal, 2-pole |
DC inputs | Plug-in terminals, 2x 1-pole |
Mains voltage input | Plug-in terminal, 2-pole |
Ambient conditions | |
Operating temperature | -5…+40 °C |
Storage temperature | -20…+70 °C |
Operating in humid environments (without moisture condensation) | 10...90 % rel. |
Storage in humid environments (without moisture condensation) | 5...90 % rel. |
Dimensions and weights | |
W x H x D mm | 260 x 80 x 38 |
Housing type | Open frame |
Weight | 680 g |
Protection category and color | |
Protection category (IEC 60529) | - |
Color | - |
Included in delivery | Adapter board Wiring Mounting material |
Standards | EN 54‑16 |
1) Use case: speech and music with maximum level
- Alarm messages with pre-announcement-tone or music, with maximum input peak level 0 dB, unlimited in time, with pilot tone 25 V, 230 V mains or 24 V batteries, operating temperature maximum +40 °C
- In speaker line loops with 'Loop isolator (100V)' PCA2005-A1 reducing 0.5 W per loop isolator
2) Use case: continuous sine tone with maximum level
- Continuous sine tone maximum input level 0 dB, unlimited in time, with pilot tone 25 V, 230 V mains or 24 V batteries, operating temperature maximum +40 °C
- In speaker line loops with 'Loop isolator (100V)' PCA2005-A1 maximum 200 W per speaker line loop and reducing 0.5 W per loop isolator