The Ethernet switches PN1001-A1 or PN2008-A1 A and B of the central network distribution hub (3) are connected to build a redundant network.
One component zone requires 2x PN1001-A1 or 2x PN2008-A1; one for A and one for B.
From the central network distribution hub, a maximum of 15 'radio links' can be connected in one branch. A 'radio link' is the connection of one component zone to the next.
Example: G1 + 14Gx = G15
1 | Ethernet switches (A and B) in one component zone (3):
|
2 | Component zone (Gn) |
3 | Central network distribution hub (CN) |
NOTICE
In this configuration, all Ethernet ports of the central network configuration hub (CN) are occupied.
No other components can be connected.