Example:

100 = 0.27 l/s

② ∆Pv100 = 9 kPa

③ kvs value required = 3.5 m3/h

∆Pv100

=

Differential pressure across the fully open valve and the valve's control path A → AB (2-port valves), AB → A (3-port diverting valves) by a volume flow 100

100

=

Volume flow through the fully open valve (H100)

∆Pmax

=

Max. permissible differential pressure across the valve's control path, valid for the entire actuating range of the motorized valve

100 kPa

=

1 bar ≈ 10 mWC

1 m3/h

=

0.278 l/s water at 20 °C