To use the functionality, both DesigoOpticNetwork and Purge extensions must be enabled

Follow the steps below to enable the extensions:

  1. Select the App Launcher icon on the top left
  1. Select the Setting tile under Advanced Apps
  • This will open a drawer with the following options: Ext, Proj, Header, Alarm, and Custom
  1. Select the Ext option to open up the extensions
  • This will open a side menu on the right where the extension will be in alphabetical order
  1. Scroll down and find the following extensions: FINNetwork and Purge
  • If the version number is green, this means that the extension is enabled
  • If the version number is red, this means that the extension is disabled
  1. Select on the extension.
  • If it the extension is disabled, a drawer will open.
  1. Select on the Enable option
  1. Refresh the page