First, the user will go to Folio app → Launch.
Once inside the Folio App, the user will select Tools option.
In the Tools list, the user will select the Subscriptions option.
Then the user will find the Create Alarm Topic option to create a new alarm topic.
After clicking it a new window will pop-up, with the following options:
Topic Name: the name of the Alarm Topic the user wishes to assign.
Alarm Priority (optional): mark as enable or disable and then set the Alarm Priority (by typing or by using the arrow), the maximum value is 255. For this the user can also set three options:
Greater-than or equal: filter all the alarms that have the priority greater-than or equal to the set value (higher number - so if priority is set to 100, it will filter anything between 100-255)
Less-than or equal: filter all the alarms that have the priority less-than or equal to the set value (lower number - so if priority is set to 100, it will filter anything between 0-100)
Exact: filter all the alarms that have the priority exactly as the set value (so if 100 is chosen, the priority must be exactly 100)
Alarm Tags (optional): returns a list of all the tags that have been added to an alarmBlock in Logic Builder program. The user can choose to include any of those tags for the alarm filter.
Custom Tags (optional): if the user is creating the alarm topic before the program, they can create their custom tags here based on what they will use on the alarmBlock. Just remember to go back to the program and add the tag to the alarmBlock.
Target Tags (optional): a list of all equips tags in case the user wants to filter the alarms based on certain equips as well
After hitting Create button, a confirmation window will appear letting the user know that the alarm topic was created.
Now the user can subscribe a user to this alarm topic subscription in the Users under Host window.
Note: You can add your own tags to your alarms by adding a tag (see screenshot below) and pressing enter.