Threshold returns true when input is above or below a setpoint with configurable deadband.
Below are couple examples of how the threshold block works.
Example 1: Setup with actAbove = true (meaning if input is above stpt)
a: in=11 sp=10 db=3 actAbove=true output=true
b: if in=8 output=true
c: if in=5 output=false
***has to go higher than 10 to be true again |
Example 2: Setup with actAbove = false (meaning if input is below stpt)
a: in=9 sp=10 db=3 actAbove=false output=true
b: if in=12 output=true
c: if in=14 output=false
***has to be lower than 10 to be true again |