If there are some numeric evaluations where units are needed to be taken into account to properly convert them accordingly, then the useUnits tag needs to be added to the program record. This will allow the control engine to use units to run any numeric evaluations, thus converting numeric values accordingly.

To add this tag to the program record, do the following:

Go to Folio → Launch

Query for program

Select the program to edit it

Add the useUnits tag and save it

That’s it, the program now should be converting the numeric evaluations