The user will need to navigate to an equip in the Equip Tree before being able to add the connector points |
1. Select on a connector underneath the BACnet tree, this will display a new view
2. In the new view, select the Discover Points button which is located on the bottom of the grid view
This will automatically discover the points for the selected connector.
Selecting Discover Points again less than a minute of the first time will load the list of points cached from the first discovery. After a minute, it will do a fresh re-discover of the points.
Re-discover button always does a fresh re-discover of points.
3. The user will be displayed with two sections:
Discovered Points: This will display available points that can be added to the connector selected
Added Points: Will list the points that have been added to an equip in the Equip Tree
4. The user will need to select on point(s) they want to add to the database
If they want to add multiple points, hold down the Alt button and click on another point to highlight more of them
5. Once the points have been selected, the user will need to select and drop the points underneath the equip they want the connector points to be located in
6. When the user drops the points, they will be displayed with a Warning prompt window asking the user if the connector points are being dropped in the correct location
7. If the user accepts, they will be directed to the Batch Record Editor form
For information on how to use this form read the following document: Batch Record Creator
8. After matching the points and selecting on the Apply button, the form will generate the points underneath the selected equip
9. The user can see the point will contain a connector ref and cur path from the location inside the connector