The graphicOn field includes tags that inform the system of the graphics to be used with specific Sites, Floors, and Equipment.
In this example, AHU runs on equipment with ahu, hvac and vavZone tags, but will not run on rooftop units.
To edit graphicOn:
Select the graphic.
Select Edit GraphicOn.The Set graphicOn window is opened.
Select FILTER.
The FILTER EDITOR is opened.
Set parameters for CONDITIONS, ALL TAGS, ANY TAGS, and CONDITION GROUPS. See Filter for additional information on how to use the Filter Editor.
Select OK.The FILTER EDITOR window is opened.
Select the CONFIRM button to confirm your selection.
The program returns to the Set graphicOn window. The updated parameters are shown in the Graphic On Filter field.
Select OK.
The graphicOn column of the Graphics list is updated.