Modbus Connectors: Backing-up the register map(s)
After creating and saving the project snapshot in Building Operator Discovery, do the following additional steps to save and backup the Register Map source for a Modbus connector:
NOTE: The CSV backup file created in this procedure must match the current name of the Register Maps for the Modbus devices in your project.
- From the DB Building project tree, select Connectors > Modbus > Register Maps > <MyMap>.
NOTE: <MyMap> is the name of a register map for one of the Modbus devices in your project.
- Select Edit Source at the bottom of the pane.
- The Edit Source dialog box displays.
- Copy the Register Map source to the clipboard.
- Save the clipboard data to a CSV file, named: <MyMap>.csv.
NOTE: "MyMap" is the name of the register map for the Modbus device selected in Step 1.
- Repeat for each register map as required.
- Keep the CSV file(s) together with the project snapshot file.
- When you are ready to restore your project backup, you will also have to restore the register map file(s). See, Modbus Connectors: Restoring the register map(s).