There are two different types of schedule points and you need to know which need the writeSchedule tag on the tuning policy:
- Assigning Tuning Policy to a Connector
- Tuning Policy tools
Regular Boolean points should NOT have the writeSchedule tag on the tuning policy.
Schedule Object points should have the writeSchedule tag on the tuning policy.
If the tuning policy has a writeSchedule tag, it sends the whole schedule data, which schedule objects know how to handle it, whereas normal boolean points do not.
To view tuning policies, enter connTuning in Folio App.
Assigning Tuning Policy to a Connector
- Drag-and-drop a tuning policy to a connector you want to assign it to.
- Once dropped, a Confirm dialog box displays.
- Refresh the Tuning Policies Tree by clicking
.
- You can select the tuning policy you created.
In the grid view, you will see a list of connectors that have been assigned to that particular connector.
Editing a Tuning Policy
- Select the Tuning Policies Tree, and then select which Tuning Policy you want to edit.
- Click Edit
.
- The Edit a Tuning Policy dialog box displays.
- Fill out the required fields and then click Apply.
Deleting a Tuning Policy
- Select the Tuning Policies Tree, and then select the Tuning Policy to delete.
- Click Delete
.
- The Warning dialog box displays, informing you that the tuning policy you selected will be permanently deleted.
- Click Delete and the changes are applied.
Tuning Policy Tools
Create / Edit a Tuning Policy
- Select the Connector Tree, and then click Tools
.
- The Tools dialog box displays.
- In the Tools dialog box, select Tuning Policy > Create/Edit Tuning Policy
- The Create or Edit Tuning Policy dialog box displays.
- In the dialog box, select Create New Tuning Policy
- The Create a Tuning Policy dialog box displays.
- The tuning policy displays in a list underneath the tuning policy tree.
Assigning Tuning Policy to a Connector
- Navigate to the connector to assign a tuning policy, and then click Tools
.
- The Tools dialog box displays.
- In the Tools dialog box, select Tuning Policy > Assign Tuning Policy.
- The Assign Tuning Policy dialog box displays.
- Select the tuning policy, and then click Apply.
- You can select the tuning policy you created.