Complete the following procedures as needed:

Configure Discover Settings

  1. From the Navigation tree, under Available Trees, expand Connectors.
  1. Expand BACnet and then click Discover.
  1. In the Added Devices pane, from the menu bar, click Discover Settings.
  • The Device Discovery Settings dialog box displays
  1. Complete the fields as required.
    NOTE: A value of 10-seconds or higher is suggested for the Timeout (seconds) value in order to allow discovery for as many BACnet devices as possible.
  1. Click Apply.

 

Manually Add a BACnet Connector

  1. From the Navigation tree, under Available Trees, expand Connectors.
  1. Expand BACnet.
  1. From the menu at the bottom of the BACnet Connectors pane, click Add.
  • The Add BACnet Connector dialog box displays.
  1. Enter the settings for your device, and then click Add.
    NOTE: For MS/TP devices the MAC Address is required.
  • The new BACnet connector displays in the BACnet Connectors pane.
  1. Select the newly added connector and then click Ping to confirm the connector integrates with the device.
  1. If the connector Status = OK and State = Open the integration was successful. Proceed to Discovering a BACnet device to discover the device and points.
  1. If an Error is reported, further investigation is required. [Add Screen capture]