When configuring a Number alarm with a Delta From Setpoint value, follow the instructions below:
- Open and launch Alarm Config from the Building Operator Discovery applications menu.
- Select the Number point filter, select Number Alarm in the Alarm Configuration drop-down, then select Add/Edit.
- In the pop-up, change the value(s) in the fields provided to meet the parameters for your point alarm. In the Compare Point Name field, copy and paste the NavName of the point you want to compare to. The point you want to compare to, must exist within the same equip as the point the alarm is being configured for.
The Compare Point Name field is case sensitive.
- Select OK when finished.