Complete the following procedures as needed:
Configure Discover Settings
- From the Navigation tree, under Available Trees, expand Connectors.
- Expand BACnet and then click Discover.
- In the Added Devices pane, from the menu bar, click Discover Settings.
- The Device Discovery Settings dialog box displays
- Complete the fields as required.
NOTE: A value of 10-seconds or higher is suggested for the Timeout (seconds) value in order to allow discovery for as many BACnet devices as possible.
- Click Apply.
Manually Add a BACnet Connector
- From the Navigation tree, under Available Trees, expand Connectors.
- Expand BACnet.
- From the menu at the bottom of the BACnet Connectors pane, click Add.
- The Add BACnet Connector dialog box displays.
- Enter the settings for your device, and then click Add.
NOTE: For MS/TP devices the MAC Address is required.
- The new BACnet connector displays in the BACnet Connectors pane.
- Select the newly added connector and then click Ping to confirm the connector integrates with the device.
- If the connector Status = OK and State = Open the integration was successful. Proceed to Discovering a BACnet device to discover the device and points.
- If an Error is reported, further investigation is required. [Add Screen capture]