Once you’ve configured point alarms, you can verify that these changes executed in Building Operator Discovery. You can do so one of two ways:
First, after you select OK in the Edit/Add pop-up, you’ll see a blue check box below a new [Alarm Type] Alarm column in the Alarm Config list results.
However, if you’re interested in seeing which value was configured to set the alarm, follow the instructions below:
- Navigate to and launch DB Builder from the Applications menu.
- Find and select the appropriate point on the device within the site hierarchy.
- Beneath Property Tags, you’ll note new tags were created. These tags outline various Alarm Config parameters, or the values that you just manually set.