• Web-responsive, mobile-friendly design with no additional graphics or programming
  • Efficient integration supported by Haystack tagging for automated configuration, more detail, and faster setup time
  • Support for nHaystack integration with legacy Niagara systems
  • Customized Templating assists integration with DXRs and other Siemens devices
  • Email alarms and reports for quick response and review
  • Notes App enables documentation of system maintenance and issues
  • Global programming in the Logic Builder allows integrated points to be programmed together for improved sequence of operation and energy savings
  • Built-in Scheduler schedules the system for day-to-day operations, special events, and holidays
  • Dashboard Builder enables quick system overview from the site or equipment level
  • Customizable widgets display deal time and historical data
  • Onboard reporting for managing system health, historical performance, and tenant usage
  • Folio 3.0 database supports clustering and replication for a faster and larger query performance
  • Greater engineering efficiency with multiple tree views and drag-and-drop functions in the new DB Builder
  • Several open-source libraries enable AM Charts and React UI tools
  • Auto-generated configuration from spreadsheets for faster project creation
  • Increased template support for Siemens controllers and devices

Bacnet Optic version 5.1.8 is supported up to BACnet 18.

Modbus Optic version 5.1.8 has compatibility with the Modbus protocol.

KNX Optic version 5.1.8 aligns with KNX standards and has compatibility with KNX ETS projects 5.7 and above.

F200 Limits

5000 points for F200 and 300 connectors limit. Over 100 connectors and 3000 points may affect system performance on high traffic networks.