This section contains information about FS20 messages, which are displayed in the Message List view. Keep in mind that only the system state for the Switch Off and Switch Off Alarming commands is updated and displayed as isolated.
Message | Description | Color |
---|---|---|
| Automatic detector fire alarm with group and detector name when the area is in unmanned mode. | Red |
| AVC alarm (pre-alarm) when the area is in manned mode. | Purple |
| Quiet message for the alarm and AVC. | Grey |
Start Investigation Time | AVC message for the beginning of the investigation time. | Blue |
Stop Investigation Time | AVC message for the finalizing of the investigation time. | Blue |
| Manual call point alarm with group and detector name. | Red |
Detector test mode [Group name] | Message for the fire detector group and single detectors. | Blue |
Detector test mode [Group name] (Grayed out) | Quiet message for detector test mode for the fire detector group and single detectors. | Grey |
Control test mode [Fire Evacuation Group Name] | Message for the fire EVAC group and parent level EVAC. | Blue |
Control test mode [Fire Control Unit Name] | Message for the fire control group and parent level control. | Blue |
Control test mode [Fire Transmission Unit Name] | Message for the fire transmission unit. | Blue |
Fire EVAC Group Name (Grayed out) | Quiet message for the fire EVAC group and parent level EVAC. | Grey |
Fire Control Group Name (Grayed out) | Quiet message the fire control group and parent level control. | Grey |
Fire Transmission Unit Name (Grayed out) | Quiet message for fire transmission unit. | Grey |
Active/[EVAC Name] | EVAC activation message for the universal EVAC parent and child level. | Green |
EVAC Name (Grayed out) | Quiet message for the universal EVAC activation. | Grey |
Active/ALERT [EVAC Name] | Message for the 2-phase EVAC. | Green |
EVAC Name (Grayed out) | Quiet message for the 2-phase EVAC. | Grey |
Active [Fire Control Name] | Message for the fire control unit for both, parent and child hierarchy. | Green |
Active [Fire Transmission Unit Name] | Message for the fire transmission unit, parent only. | Green |
Fire Control Unit Name (Grayed out) | Quiet message for the fire control unit. | Grey |
Fire Transmission Unit Name (Grayed out) | Quiet message for the fire transmission unit. | Grey |
Test activation [Group/Detector Name] | Message for the fire detector group and single detectors, when the fire detector group is in revision mode. | Blue |
Test activation [Universal EVAC Name] | Message for the fire universal EVAC unit, both parent and child level, when the fire EVAC group is in revision mode. | Blue |
Test activation [2-Phase EVAC Name] | Message for the fire 2-phase EVAC unit, both parent and child level, when the fire EVAC group is in revision mode. | Blue |
Test activation [Fire Control Unit Name] | Message for the fire control unit, both parent and child level, when the fire control group is in revision mode. | Blue |
Test activation [Transmission Unit Name] | Message for the fire transmission unit, when the revision mode on. | Blue |
Quiet | Quiet message for all test activation with all kind of groups. | Grey |
Manned Operation [Area Name] | Message, when changing the area from unmanned to manned. | Blue |
Unmanned Operation [Area Name] | Quiet message for unmanned operation, when changing the area from manned to unmanned. | Grey |
Not configure | FS20 loop message. | Blue |
Release | Message for releasing the key box. | Blue |
Open | Message for opening the key box. | Blue |
Close | Message for closing the key box. | Blue |
Key Box Name (Grayed out) | Quiet message for the key box release. | Grey |
Sabotage [Key Box Name] | Sabotage message for the key box. | Purple |
Key Box Name (Grayed out) | Quiet message for the key box release sabotage. | Grey |
Detector missing [Detector Name] | Fault message. | Yellow |
Detector Name (Grayed out) | Quiet message for the detector on. | Grey |
Detector wire break. | Fault message. | Yellow |
Short circuit. | Fault message. | Yellow |
Loop/Stub Break. | Fault message. | Yellow |
Device Power off. | Fault message. | Yellow |
Battery Failure | Fault message. | Yellow |
Lost OIS connection | Fault message. | Yellow |
Synchronization with Subsystem for component FS20 lost. | Fault message. | Yellow |
| Sinteso view message, if the Sinteso view is connected. | Blue |