You can only configure the event filtering for orders that are not related to logical events.
- A site and a gateway have been created.
- In the navigation pane, select the site and afterwards the gateway that you have created.
- Select the SIPORT Vu-Handler unit.
- In the Configuration Files tree, click the event_filter.csv file.
- Remove # in front of the message you want to filter out.
- Click
.
- Switch to the corresponding gateway.
- Click Upload.
- Switch to the Siveillance Control engineering client and start the OIS component. For more information refer to: Starting OIS Connections in Configuration.
- To filter controller messages and general device messages, remove # from the following events:
- #285;Device offline - No communication
- #286;Device online again - Communication again working
- #289;Device tamper - Sabotage-Alarm
- #290;Device tamper again ok - End Sabotage