For each gateway, one PLC unit is created automatically. This unit processes the incoming data and controls the outputs from both the Cu- and Vu-Handler units. You can modify attributes of a PLC unit.
This information applies to the following subsystems:
D100, FS20, IC Transliner, SIGMASYS, SiPass, SIPORT, SPC and Desigo CC.
- In the navigation pane, select the site and afterwards the gateway.
- Select the plc unit.
- Check that the package attribute corresponds to the selected subsystem. The package attribute defines the list of CL packages to be started.
Subsystem | Package |
---|---|
D100 | clvbf |
FS20 | clfs20 |
IC Transliner | cltransliner |
SIGMASYS | clvbf |
SiPass | clsipass-dm |
SIPORT | clsiport-dm |
SPC | cuspc |
Transliner Pro (NOX) | cltransliner |
Desigo CC | cldesigocc-dm |
- To change the language for language-dependent elements, edit the language attribute in the Optional attributes tab. Language-dependent elements can be alarm messages coming from the subsystem. de_DE (default) and en_GB languages are available.
- Click Submit.
- Continue with the Cu-Handler unit configuration. For more information refer to: Configuring the Cu-Handler Unit and Devices.