Small automation control projects with:
- Some primary plants
- Some touch panels
- Some KNX PL-Link field devices
- Total number of data points (physical and integration): 50 to 300
- Total number of devices (PXC, DRA, and third-party): up to 20
- Optional: Cloud connectivity to Building X for remote access and data points time series
Examples: Small schools, small office buildings, etc.
Installation
- Cabling: Patch cables (CAT5/6/7 up to 100 meters) between PXC devices. Each PXC4/5/7 device has a switch with two ports for easy connection. Protect cabling against unauthorized access.
- Connection to ABT Site Tool either as indicated on the onboard switch or via WLAN.
Set up network information for each device (via ABT Site Tool):
- Each PXC device needs a unique address
- IP port: Default value BAC0