Use the router PXG3.L / PXG3.M with HW Index C only.
Data point integration: LonWorks devices take a lot longer than IP devices due to the lower network speed. Reference value: Approximately 30 times longer (depending on the project setup).
To avoid timeout problems,
- Use the workflow: Data point integration.
- Integrate at the standard user level
- Avoid the "Cache" dialog
- Create templates for individual data point selection for LON devices on IP devices.
These templates can then be imported to the LON devices.