Data point capacity is limited for graphical operation (data point integration).

The figures below apply to integration over the standard user level and where full graphical operation of all data points is required.

 

Desigo primary plant

Desigo room automation

Access level for integration

Extended operation

Standard operation

Max. number *

Number of hardware-I/Os **

Number of simple rooms (HVAC only)

Number of complex rooms (HVAC, lighting, shading)

PXG3.W100-2

400

30

10

PXG3.W200-2

800

60

20

PXM30.E

200

15

5

PXM40.E

400

30

10

PXM50.E

400

30

10

PXM30-1, PXM40-1, PXM50-1

n.a. (see limits for PXG3.Wx00-2)

*

The selection of integrated data points can be optimized and individually customized with the Advanced Tool in the data point integration function.

**

Primary plants: Per hardware I/O some 2.5 BACnet objects are integrated on average.