WARNING
Hazardous pressure

Before pressurizing the system, make sure that all the valves are correctly mounted and secured.

Always assume that the discharge network and the selector valves are pressurized.

  • Before any operation on the system, make sure that the system components are not pressurized.
  • Ensure that the safety and protection equipment that is already in place has been properly mounted and commissioned.
  • For safety reasons, the pneumatic drive must be pressurized gradually when used for the first time.
  • When programming the ECP, ensure that the extinguishant cylinders associated to a protected zone cannot be activated before the actuation of the corresponding solenoid valve and selector valve.