Warning: These circuits are intended for 24 hour alarm monitoring only.

UL 1076 requires an HTSW-1 tamper switch as well as a PAL-1 printer. Only Models HTRI-S/-D/-R and XTRI-S/-D/-R may be used as security points. A COMMUNICATION FAILURE with an HTRI or XTRI device configured for SECURITY results in a SECURITY EVENT as well as a communication trouble. When installing an HTRI or XTRI device in the Zeus tool, be sure to set the device usage to security; otherwise, the device usage defaults to fire alarm.

If any input or output on a device is configured for Security usage in the Zeus tool, all other inputs and outputs on that device must be set for Security usage. It is not permitted to mix Security and other usages on the same device. This limitation does not apply to Canada.

Caution

  • When setting the device address using the DPU, select the normally closed alarm causing input.
  • Connect only one switch per HTRI or XTRI input.

For proprietary burglary application (UL 1076):

  • Use an HTSW-1 tamper switch to monitor the main enclosure.
  • Monitor each HTRI-S/-D/-R/-M and XTRI-S/-D/-R/-M related to this application for 24 hours by using a listed motion detector (to prevent tampering).
  • Monitoring of security points is performed at the Cerberus PRO Modular. The Cerberus PRO Modular is suitable for installation at either the protected premises or remotely as a receiving unit.

Notes

1. All supervised switches must be held closed and/or open for at least a quarter of a second to guarantee detection.

2. End of line device: 470 ohm, ¼W resistor, P/N 140-820164.

For Canadian applications, use Model EL-33 with 470 ohm, ¼W resistor.

3. HTRI is polarity insensitive. Line 1 and Line 2 can be either line of the loop.

4. Electrical ratings:

Voltage maximum: 30 VDC

Current maximum: 1.3mA during polling

5. Supervised switch ratings:

  • Voltage maximum: 27 VDC
  • Current maximum: 6mA during polling
  • Contact resistance maximum: 10 ohms
  • Maximum cable length: 200 feet (18 AWG)
  • CLine to line: 0.02uF
  • CLine to shield: 0.04uF
  • Max line size: 14 AWG
  • Min line size: 18 AWG

6. Relay contact ratings:

  • 4A, 125 VAC resistive
  • 4A, 30 VDC resistive

Inductive:

  • 3.5A, 120 VAC (0.6P.F.)
  • 3.0A, 30 VDC (0.6 P.F.)
  • 2.0A, 120 VAC (0.4 P.F.)
  • 2.0A, 120 VAC (0.35 P.F.)
  • 2.0A, 30 VDC (0.35 P.F.)

The relay is shown in standby condition.

7. Terminal 5 must be connected to earth ground.

a. Use wire nuts to pass the shield wire through the electrical box with NO connection to the device terminal block or to local ground.

b. Use shielded wire to connect the switch wiring.

c. Tie the switch wiring shield to terminal 5 or the local earth ground.

8. For proprietary burglary application:

a. Use an HTSW-1 tamper switch to monitor the main enclosure.

b. Monitor each HTRI-S/-R/-D related to this application continuously by using a listed motion detector (to prevent tampering).

9. In supervisory:

  • HTRI-S/-R draws 1.3mA
  • HTRI-D draws 1.3mA

10. Positive and negative ground fault detected at <60K ohms for terminals 3 and 4.

HTRI-S-R and HTRI-D Wiring

Terminal 5 of the HTRI-S/-D/-R must be connected to a known good earth ground for proper operation.

Notes

1. All supervised switches must be held closed and/or open for at least a quarter of a second to guarantee detection.

2. End of line device: 470 ohm, 1% 1/2W resistor, P/N A5Q00073045, and use Model TB-EOL with 470 ohm, 1% 1/2W resistor.

3. For polarity insensitive wiring, Line 1 and Line 2 can be either line of the device loop.

4. Supervised switch ratings:

  • Voltage maximum: 27 VDC
  • Current maximum: 6mA during polling
  • Contact resistance maximum: 10 ohms
  • Maximum cable length: 200 feet (18 AWG)
  • CLine to line: 0.02uF
  • Max line size: 14 AWG
  • CLine to shield: 0.04uF
  • Max line size: 14 AWG
  • Min line size: 18 AWG

5. Relay contact ratings:

  • 4A, 125 VAC resistive
  • 4A, 30 VDC resistive

Inductive:

  • 3.5A, 120 VAC (0.6 P.F.)
  • 3.0A, 30 VDC (0.6 P.F.)
  • 2.0A, 120 VAC (0.4 P.F.)
  • 2.0A, 120 VAC (0.35 P.F.)
  • 2.0A, 30 VDC (0.35 P.F.)

The relay is shown in standby condition.

6. In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be

isolated between two modules in isolator mode in a Class A wiring.

7. In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated behind one module in isolator mode in a Class B wiring.

8. HLIM isolator module and SBGA-34 sounder base cannot be used in the same loop with the modules in isolator mode.

XTRI-R Polarity Insensitive Mode Wiring
XTRI-R Isolator Mode Wiring
XTRI-D Polarity Insensitive Mode Wiring
XTRI-D Isolator Mode Wiring
XTRI-S Polarity Insensitive Mode Wiring
XTRI-S Isolator Mode Wiring

(Refer to Figures 25 and 26) Refer to the wiring diagram and wire the XTRI-M addressable interface module accordingly.

Note: Recommended wire size:

  • 18 AWG minimum
  • 14 AWG maximum
XTRI-M Isolator Mode Wiring
XTRI-M Polarity Insensitive Mode Wiring

Notes

1. All supervised switches must be held closed and/or open for at least a quarter of a second to guarantee detection.

2. The drawing shown here is ONLY to supervise wire open, end of line device: 470 ohm, 1% 1/2W resistor, P/N A5Q00073045. Use Model TB-EOL with 470 ohm, 1% 1/2W resistor.

3. When the XTRI-M is wired in polarity insensitive mode, Line 1 and Line 2 can be either line of the loop.

4. The supervised switches have the following ratings:

  • Voltage maximum: 27 VDC
  • Current maximum: 6mA during polling
  • Contact resistance maximum: 10 ohms
  • Maximum cable length: 200 feet (18 AWG)
  • CLine to line: 0.02uF
  • Max line size: 14 AWG
  • CLine to shield: 0.04uF
  • Max line size: 14 AWG Min line size: 18 AWG

Caution: Ground shield of device line ONLY at the specified location on the Control Panel.

Caution: EOL device must be a 470 ohm, 1% 1/2W resistor for wire open supervision.

5. The unshielded wire can be used at input to monitor the switch contact. No ground lead is provided.

6. All circuits are power limited.

7. Positive and negative ground fault detected at <25K ohms for the input wiring (ORANGE leads).

8. In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated between two modules in isolator mode in a Class A wiring.

9. In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated behind one module in isolator mode in a Class B wiring.

10. HLIM isolator module and SBGA-34 sounder base cannot be used in the same loop with the modules in isolator mode.