System Indication

All voice system faults are reported at the FCM2041-U3, and at the programmed speaker group control switch. The operator at the FCM2041-U3 is able to ACK, SILENCE/UNSILENCE and RESET voice system events. For example, in the event of an ALL EVAC, the Audibles LED on the FCM2041-U3 comes on and the Silence Audibles soft key displays on the FCM2041-U3 so the system can be silenced from the FCM2041-U3.

Automatic Operation

The voice system interfaces automatically to the fire alarm/mass notification system using the speaker functions in the Function view of the Zeus Programming tool. In reaction to events from the fire alarm/mass notification system (DLC/XDLC devices), the voice alarm system activates its pre-programmed alarm procedures. In fire applications, the voice alarm system typically broadcasts an alarm signal, which is immediately followed with a prerecorded message on the fire floor, the floor above and the floor below. It is common to have two stage alarms, with evacuation in some areas and alert in others. LEDs indicate the current system status and the floors in which the evacuation or alert signal is sounding.

Since this sequence has occurred automatically, only the events that were predetermined in the original system evacuation plan and programmed into the system configuration program will occur.

Evacuation Signal (EVAC)

EVAC sends the evacuation tone or message (predetermined in system design) to all or selected speaker groups in the building requesting that the occupants evacuate. A steady red LED indicates whether the evacuation signal (tone or message) is being sent to the entire building or to selected areas of the building.

It is possible to have two different evacuation signals, EVAC 1 and EVAC 2. EVAC 2 will be overridden by EVAC 1 to the same speaker group. Either EVAC signal will be overridden by an emergency page to the same speaker group.

Alert Signal

Alert signal sends the alert tone or message (predetermined in system design) to all or selected speaker groups in the building to alert occupants to the alarm condition. A flashing red LED indicates whether the ALERT signal (tone or message) is being sent to the entire building or selected areas.

It is possible to have two different alert signals, ALERT 1 and ALERT 2. ALERT 2 will be overridden by ALERT 1 to the same speaker group. The alert signal will be overridden by an emergency page or an evacuation signal to the same speaker group.

Manual Operation

After a few minutes of automatic operation, the voice alarm system can be taken over manually by authorized personnel.

Manual voice operation functions such as emergency paging, evacuation or alert signal activation, firefighters' telephone operation, multiple voice system command center operation, as well as convenience page or background music operation are possible at any time.

Emergency Page

Emergency Page allows a live voice page from the emergency microphone to all or selected speaker groups in the building. An optional preannouncement tone precedes emergency pages for a duration of time set in the Zeus programming tool.

Convenience Page

Convenience Page allows a live voice page from the convenience page microphone to all or selected speaker groups in the building. Convenience pages are a low priority function and will be overridden by an emergency page, an evacuation or an alert signal to the same speaker group.

Background Music

Background Music sends background music from an external audio input to all or selected speaker groups in the building. Background Music is the lowest priority and will be overridden by an emergency page, an evacuation or alert signal and a convenience page to the same speaker group.

Convenience Page and Background Music may only be used in Legacy Mode.