Overview
The application function "Central emergency HVAC 11, fire emergency" (CenEmgHvac11) handles emergency functions for connected rooms and coordinates subordinate AFs.
DMS | Danger management system |
Fire det | Fire detector |
SmextSu | Smoke extraction supply air |
SmextEh | Smoke extraction exhaust air |
Cen | Central functions |
CenEmgHvac11 | Central emergency HVAC 11, fire emergency |
R | Room |
RHvacCooxx | Room HVAC coordination set 11, for fan coil unit, radiant ceiling, radiator, radiant floor / 12 / 13 / 17 |
PltModDtr | Plant mode determination function |
RSegm | Room segment |
Hvacxx | HVAC Set |
Function
The fire detection and the evaluation of the correct HVAC emergency operating mode for a fire area and the primary plants is done by a danger management system, not by Desigo Room Automation.
Fire could result in death or serious injury. Therefore ...
- use Desigo Room Automation fire solutions for non live-critical applications with limited health and cost risks only,
or
- get an individual approval by local fire authorities for a specific project.
Input
The HVAC Emergency operating mode is commanded by the danger Management System
- via 1...3 hardwired contacts.
- via BACnet (command value).
Output
Desigo Room Automation is used to distribute the HVAC emergency operating mode to the connected rooms, and to control the HVAC devices according to the emergency mode.
The HVAC emergency operating mode is written cyclically with a configurable cycle time.
One AF CenEmgHvac11 is responsible for one fire area, where all rooms are controlled in the same HVAC emergency operating mode. This does not necessarily mean that these rooms are in the same supply chain.
Group operation can be hierarchic: Central emergency operation (e.g. entire building) passes on the command to subordinate emergency operations (e.g. floor).
The following emergency operating modes are supported:
HVAC Emergency operating mode | Description |
|---|---|
None | None |
Emerg.off | Air volume flow off |
Negative press. | Smoke extraction positive pressure |
Positive press. | Smoke extraction negative pressure |
Purge | Purge |
Interface to the Danger Management System
The AF features a hardwired interface to the danger management system.
1...3 volt-free contacts can be connected to 1...3 binary inputs to indicate the required HVAC emergency operating mode
FireDet (always required) | SmextEh (requires AF CenSmextEh) | SmextSu (requires AF CenSmextSu) | Resulting HVAC emergency mode |
|---|---|---|---|
Inactive | Irrelevant | Irrelevant | None |
Active | Inactive | Inactive | Emerg.off |
Active | Inactive | Active | Positive press. |
Active | Active | Inactive | Negative press. |
Active | Active | Active | Purge (features CenSmextSu and CenSmextEh) |
The AF also features a BACnet interface (CmdVal), which can be operated by the danger management system.
The same interface (HW and BACnet) is featured by the primary system (CP{Ahu80}). It is recommended to control the primary system directly hardwired by the danger management system. However, as a backup, AF SplyAir11 also evaluates the HVAC emergency operating mode for the primary system of a supply chain.
Secure communication
Group managers and group members monitor communication.
HVAC components go to secure positions if the group manager is unavailable.
Testing
The AF features a test interface (a BACnet configuration value) which supports testing of the emergency reactions regardless of the input conditions on the hardwired interface.
Hierarchical grouping
This AF supports hierarchical grouping. For detailed information, see Hierarchical grouping.
With hierarchical grouping, CenEmgHvac11 can either distribute its outputs directly to the connected rooms or to subsequent AFs of same type.
Interface to local and superordinate functions: Both local inputs and an optional superior AF access the same BA object. Arbitration is done via priority handling. The local emergency input has higher priority (lower number) than the emergency command from a superordinate central function.
Configuration
Parameters
Description | Parameter | Default value |
|---|---|---|
Cycle 0...60 [min] | Cycle | 15 [min] |
Enable fire detector 0:No | EnFireDet | 1:Yes |
Important in case of hierarchical grouping
When used as a superordinate AF, the AF has to ensure that in case of a missing / invalid fire detector a value is commanded that ensures a secure position.
When used as a subordinate AF for distributing values, the AF does not have to respond to a missing / invalid fire detector.
As the AF cannot differentiate these two cases, it must be configured.