Supply voltage GDB1..1E | |||
|---|---|---|---|
|
Operating voltage (SELV/PELV) | AC 24 V ~ ±20 % (19.2...28.8 V ~) DC 24...48 V ⎓ ±20 % (19.2...57.6 V ⎓) 1) | ||
Frequency | 50/60 Hz | ||
Power consumption | Operation | GDB14..1E | 1.0 VA / 0.6 W |
GDB16..1E | 1.3 VA / 1.0 W | ||
Holding state | GDB14..1E | 0.7 VA / 0.4 W | |
GDB16..1E | 1.0 VA / 0.6 W | ||
Supply voltage GDB3..1E | |||
|---|---|---|---|
|
Operating voltage (SELV/PELV) | AC 100...240 V ~ ±10 % (90...264 V ~) | ||
Frequency | 50/60 Hz | ||
Power consumption | Operation | GDB34..1E | 5.0 VA / 1.6 W |
GDB36..1E | 3.3 VA / 1.2 W | ||
Holding state | GDB34..1E | 0.9 W | |
GDB36..1E | 0.5 W | ||
Operating data | ||
|---|---|---|
|
Nominal torque | Nominal | 5 Nm |
Maximum (blocked) | 10 Nm | |
Minimum (hold state) | 5 Nm | |
Nominal rotation angle | Nominal (with position indicator) | 90° |
Maximum (mechanically limited) | 95° ±2° | |
Runtime at nominal angle of rotation 90° | 150 s | |
Sound pressure level: Actuator | 28 dB(A) | |
Inputs | |||
|---|---|---|---|
|
Positioning signal for GDB14..1E | Operating voltage | wires 1-6/G-Y1 | Clockwise |
wires 1-7/G-Y2 | Counterclockwise | ||
Positioning signal for GDB34..1E | Operating voltage | wires 4-6/N-Y1 | Clockwise |
wires 4-7/N-Y2 | Counterclockwise | ||
Positioning signal for GDB16..1E | Input voltage | wires 8-2/Y-G0 | DC 0/2...10 V ⎓ |
Power consumption | 0.1mA | ||
Input resistance | ≥100 kΩ | ||
Max. permissible input voltage | DC 35 V ⎓ limited internally to DC 10 V ⎓ | ||
Protected against incorrect wiring | Max. AC 24 V ~/ DC 24...48 ⎓ | ||
Hysteresis | for non-adjustable characteristic function | 60 mV | |
for adjustable characteristic function | 0.6 % of ΔU | ||
Adjustable characteristic function (GDB163.1E, GDB164.1E) | |||
Adjustable with 2 potentiometers | Starting point Uo | DC 0...5 V ⎓ | |
Workspace ΔU | DC 2...30 V ⎓ | ||
Max. input voltage | DC 35 V ⎓ | ||
Protected against incorrect wiring | max. AC 24 V ~ / DC 24...48 V ⎓ | ||
Outputs | |||
|---|---|---|---|
|
Position indicator | Output signal GDB16..1E | wires 9-2/U-G0 | |
Output signal GDB36..1E | wires 9-2/U-G- | ||
Output voltage U | DC 0...10 V ⎓ | ||
Max. output current | DC ±1 mA | ||
Protected against incorrect wiring | max. AC 24 V ~ / DC 24...48 V ⎓ | ||
Aux. power supply (G-/G+) | GDB36..1E | DC 24 V ⎓ ±20 %, max. 10 mA | |
Feedback potentiometer (for GDB142.1E) | Change in resistance | wires P1-P2 | 0...5000 Ω |
Load | <0.25 W | ||
Max. loop current | <0.1 mA | ||
Permissible voltage at potentiometer (SELV/PELV) | AC 24 V ~ / DC 24...48 V ⎓ | ||
Insulation resistance between potentiometer and housing | AC 500 V ~ | ||
Mechanical life | |
|---|---|
|
Full cycles | 100'000 |
Partial cycles | 5'000'000 |
Auxiliary switches (GDB146.1E, GDB166.1E, GDB346.1E) | ||
|---|---|---|
|
Switching voltage | AC 24..250 V ~ / DC 12...30 V ⎓ | |
Contact loading | 6 A resistive, 2 A inductive, min. 10 mA @ AC 4 A resistive, 2 A inductive, min. 10 mA @ DC 30 V ⎓ 0.8 A resistive, 0.5 A inductive, min. 10 mA @ DC 60 V ⎓ | |
Electric strength auxiliary switch against housing | AC 4 kV | |
Switching range for auxiliary switches | 5...90° | |
Setting increments | 5° | |
Factory setting | Switch A | 5° |
Switch B | 85° | |
Connecting cable | |
|---|---|
|
Cable, length | 0.9 m |
Cable, cross-section | 0.75 mm2 |
Permissible length for signal wires | 300 m |
Safety class and degree of protection | ||
|---|---|---|
|
Protection class | AC 24 V / DC 24...48, feedback potentiometer | III |
AC 100...240 V, auxiliary switch | II | |
Degree of protection of housing | IP54 per EN 60529 | |
Environmental conditions | ||
|---|---|---|
|
Operation according to | Climatic conditions | Class 3K5 |
Mounting location | Interior, weather-protected | |
Temperature (extended) | -32...55 °C | |
Humidity, non-condensing | <95 % r.h. | |
Transportation according to | Climatic conditions | Class 2K3 |
Temperature (extended) | -32...70 °C | |
Humidity, non-condensing | <95 % r.h. | |
Storage according to | Climatic conditions | Class 1K3 |
Temperature (extended) | -32...50 °C | |
Humidity, non-condensing | <95 % r.h. | |
Mechanical conditions | Class 2M2 | |
Standards, directives and approvals | |
|---|---|
|
Product standards | EN 60730 |
Electromagnetic compatibility (field of use) | For residential, commercial, and industrial environments |
EU conformity (CE) | A5W00003842 2) |
UK conformity (UKCA) | A5W00198029A 2) |
RCM Conformity | A5W00003843 2) |
EAC compliance | Eurasian conformity |
UL certification | UL per UL 60730 http://ul.com/database cUL as per CSA-C22.2 No. 24-93 |
Environmental compatibility |
|---|
|
Environmental Declaration A5W00026066 2) contains data on environmental-compatible product design and assessment (RoHS compliance, compositions, packaging, environmental benefits and disposal). |
Dimensions and weight | ||
|---|---|---|
|
Actuator (W x H x D) | See Dimensions | |
Damper shaft | Round | 8...16 mm |
Round with insert | 8...10 mm | |
Square | 8...12.8 mm | |
Hexagonal | 8...14 mm | |
Min. length | 20 mm | |
Max. shaft hardness | <300 AV | |
Weight (excluding packaging) | Without switch | Max. 0.49 kg |
With switch | Max. 0.63 kg | |
|
1) | C-UL: Permissible only to DC 30 V ⎓ |
2) | The documents can be downloaded at http://siemens.com/bt/download. |
3) | This value only works with the form-fit insert. |