Parameter list

Parameter

Description

Factory setting

Setting range

Remark

P01

Control behavior

PID slow (4)

0 = 2P, 1.0 K

1 = 2P, 0.5 K

2 = PID fast

4 = PID slow

 

P02

Maximum temperature range

30 °C

P03…30 °C

Limit of comfort and economy setpoint

P03

Minimum temperature range

5 °C

5 °C…P02

Limit of comfort and economy setpoint

End

Exit parameter setting

 

 

 

Parameter setting

The parameter setting remains in non-volatile memory and is not erased when the battery is removed. The reset function on the rear of the thermostat reloads the factory settings.

Parameter setting mode

  1. Press LEARN on the rear for 5 seconds until “P01” appears.
  2. Press LEARN again and, the parameter value on the second line flashes and is ready for adjustment.
  3. Adjust the parameter using setting knob.
  4. Press LEARN once to confirm the setting.
  5. Rotate the setting knob clockwise to next parameter and repeat steps 2 to 4.
  6. Exit parameter setting mode by rotating the setting knob clockwise to “End” and pressing LEARN once.

Note: The thermostat automatically exits parameter setting mode one minute after the last action.