When mounting the transmitter, attach the baseplate first. You need to mount the transmitter on a flat wall. (For details, refer to the separate mounting instructions A6V10974421.)
The transmitter comes with a fold-out stand and may be used as a “mobile” device.
Mounting the receiver does not require a baseplate. Connect the electrical connections first and then fit and secure the receiver in compliance with local regulations. (For details, refer to the separate mounting instructions A6V10974421.)
EMI filter (e.g., KEILS EMI CW4L2-3-R) can be used to reduce EMI disturbance. (For details, see Connection diagram.)
- Disconnect from power supply before connecting EMI filter.
- Make sure EMI filter is out of reach after installation.
If the reference room contains thermostatic radiator valves, set them to their fully open position.
For commissioning, refer to the operating instructions A6V101035988.
Communication of the RDH100RF/SET (transmitter and receiver) is paired ex factory.
- The devices are suitable for wall mounting.
- Recommended height: 1.5 m above the floor.
- Do not mount the devices in recesses, shelves, behind curtains or doors, or above or near heat sources.
- Avoid direct solar radiation and drafts.
- Seal the conduit box or the installation tube if any, as air currents can affect sensor readings.
- Adhere to allowed ambient conditions.