The multistate VAV supply changeover condition input signal (VavSuChovrCnd) comes from the room coordinating function (RCoo). It indicates the current heating / cooling available status for central AHU. Four states are supported:
- Neither
- Heating
- Cooling
- Neutral
"Neutral" means that heating and cooling PID controllers are both enabled and that the system is providing air that is not hot or cold.