Vnom (nominal volume flow) [m3/h, l/s, cfm] - Basic Documentation - GDB181.1E/BA - GDB181.1EMBA - GLB181.1E/BA

VAV Compact Controller BACnet MS/TP G..B181.1E/BA

Product Family
OpenAir
Product Group
Damper actuators
Content Language
English
Content Type
Basic Documentation
Product Version
Status
Valid
Date
2021-10-26
Document No
A6V10631864_en--_g
Download ID
A6V10695831
Stock No.
S55499-D168
S55499-D169
S55499-D506
Product No.
GDB181.1E/BA
GDB181.1EMBA
GLB181.1E/BA

VAV boxes are ordered through an OEM according to this nominal volume flow and min. / max. volume flow settings. The maximum volume flow for ventilating a room / zone can’t be higher than the nominal volume flow. Often the maximum volume flow is lower than Vnom for potential future expansions of volume flows