Status / statistics - Basic Documentation - GDB181.1E/BA - GDB181.1EMBA - GLB181.1E/BA

VAV Compact Controller BACnet MS/TP G..B181.1E/BA

Product Family
OpenAir
Product Group
Damper actuators
Content Language
English
Content Type
Technical Documentation > Basic Documentation
Product Version
Status
Valid
Date
2021-10-26
Document No
A6V10631864_en--_g
Download ID
A6V10695831
Stock No.
S55499-D168
S55499-D169
S55499-D506
Product No.
GDB181.1E/BA
GDB181.1EMBA
GLB181.1E/BA
Access level
Internet
File Type
html
ID Obj. Type Object Name Property Name Prop. ID Resolution / Enumerations

0

BI

LocalOverride

LocalOverride

PV

1 = active
0 = inactive

1

BI

BackupMode
Entered

BackupModeEntered

PV

1 = active
0 = inactive

2

BI

Device Jammed

DeviceJammed

PV

1 = active
0 = inactive

3

BI

NominalLife-timeExceeded

NominaLifetimeExceeded

PV

1 = active
0 = inactive

4

BI

Invalid
Configuration

InvalidConfiguration

PV

1 = active
0 = inactive

0

MSI

Pressure SensorState

PressureSensorState

PV / ST

1 = No error
2 = Connection fault
3 = Comm. fault

1

MSI

SelftestStatus

SelfTestStatus

PV / ST

1 = Not tested
2 = Selftest failed
3 = Selftest passed

2

MSI

AdaptionState

AdaptionState

PV / ST

1 = Adaption not done
2 = Adaption done
3 = Adaption in progress

6

PIV

Cumulated Uptime

CumulatedUpTime

PV

0..232 s

7

PIV

Cumulated Running Time

CumulatedRunningTime

PV

0..232 s

8

PIV

Counter Repositioning

CounterRepositioning

PV

0..232 s

9

PIV

CounterPower Up

CounterPowerUp

PV

0..232 s

10

PIV

CounterDevice Jam

CounterDeviceJam

PV

0..232 s

Abbreviations:

BACnet Property ID

PV

Present Value

SF

Status Flags

CI

COV Increment

ST

State Text

Object Type

D

Device

MSI

MultiStateInput

MSV

MultiStateValue

PIV

PosIntValue

BI

BinaryInput

BV

BinaryValue

AI

AnalogInput

AO

AnalogOutput

AV

AnalogValue