Communication parameters - Basic Documentation - GDB181.1E/BA - GDB181.1EMBA - GLB181.1E/BA

VAV Compact Controller BACnet MS/TP G..B181.1E/BA

Product Family
OpenAir
Product Group
Damper actuators
Content Language
English
Content Type
Basic Documentation
Product Version
Status
Valid
Date
2021-10-26
Document No
A6V10631864_en--_g
Download ID
A6V10695831
Stock No.
S55499-D168
S55499-D169
S55499-D506
Product No.
GDB181.1E/BA
GDB181.1EMBA
GLB181.1E/BA
ID Obj. Type Object Name Property Name Prop. ID Range / Enum. Default

3

PIV

MSTP -Address

MacAddress

PV

0..128

1

4

PIV

DevObj-ID-Base

DevObjIdBase

PV

0..4‘194‘303

10’000

5

PIV

MaxMaster

MaxMaster

PV

1..127

127

7

MSV

Baudrate

Baudrate

PV / ST

1 = auto
2 = 9600
3 = 19200
4 = 38400
5 = 57600
6 = 76800
7 =115200

1

0

BV

BusTermination

BusTermination

PV

0 = Off

1 = On

0

8

MSV

Bus Config.
Command

BusConfig
Command

PV

1 = Ready

2 = Load
3 = Discard

1