Object type | Supported | Can be created dynamically | Can be deleted dynamically |
---|---|---|---|
Analog Input | π· | π | π |
Analog Output | π· | π | π |
Analog Value | π· | π | π |
Binary Input | π· | π | π |
Binary Output | π | π | π |
Binary Value | π· | π | π |
Calendar | π | π | π |
Command | π | π | π |
Device | π· | π | π |
Event Enrollment | π | π | π |
File | π | π | π |
Group | π | π | π |
Loop | π | π | π |
Multi-State Input | π· | π | π |
Multi-State Output | π | π | π |
Notification Class | π | π | π |
Program | π | π | π |
Schedule | π | π | π |
Averaging | π | π | π |
Multi-State Value | π· | π | π |
Trend Log | π | π | π |
Life-Safety-Point | π | π | π |
Life-Safety-Zone | π | π | π |
Accumulator | π | π | π |
Pulse-Converter | π | π | π |
Event Log | π | π | π |
Global Group | π | π | π |
Trend Log Multiple | π | π | π |
Load Control | π | π | π |
Structured-View | π | π | π |
Access Door | π | π | π |
(unassigned) | π | π | π |
Access Credential | π | π | π |
Access Point | π | π | π |
Access Rights | π | π | π |
Access User | π | π | π |
Access Zone | π | π | π |
Credential Data Input | π | π | π |
Network Security | π | π | π |
Bitstring Value | π | π | π |
Characterstring Value | π | π | π |
Object type | Supported | Can be created dynamically | Can be deleted dynamically |
---|---|---|---|
Date Pattern Value | π | π | π |
Date Value | π | π | π |
Datetime Pattern Value | π | π | π |
Datetime Value | π | π | π |
Integer Value | π | π | π |
Large Analog Value | π | π | π |
Octetstring Value | π | π | π |
Positive Integer Value | π· | π | π |
Time Pattern Value | π | π | π |
Time Value | π | π | π |
Analog Input
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | π· | R | |
Object_Name | π· | R | |
Object_Type | π· | R | |
Present_Value | π· | R | |
Description | π· | R | |
Device_Type | π· | R | |
Status_Flags | π· | R | |
Event_State | π· | R | |
Reliability | π· | R | |
Out_Of_Service | π· | W | |
Update_Interval | π | ||
Units | π· | R | |
Min_Pres_Value | π· | R | |
Max_Pres_Value | π· | R | |
Resolution | π· | R | |
COV_Increment | π· | W | |
Time_Delay | π | ||
Notification_Class | π | ||
High_Limit | π | ||
Low_Limit | π | ||
Deadband | π | ||
Limit_Enable | π | ||
Event_Enable | π | ||
Acked_Transitions | π | ||
Notify_Type | π | ||
Event_Time_Stamps | π | ||
Profile_Name | π· | R |
Analog Output
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | π· | R | |
Object_Name | π· | R | |
Object_Type | π· | R | |
Present_Value | π· | W | |
Description | π· | R | |
Device_Type | π· | R | |
Status_Flags | π· | R | |
Event_State | π· | R | |
Reliability | π· | R | |
Out_Of_Service | π· | R | |
Units | π· | R | |
Min_Pres_Value | π· | R | |
Max_Pres_Value | π· | R | |
Resolution | π· | R | |
Priority_Array | π· | R | |
Relinquish_Default | π· | R | |
COV_Increment | π | ||
Time_Delay | π | ||
Notification_Class | π | ||
High_Limit | π | ||
Low_Limit | π | ||
Deadband | π | ||
Limit_Enable | π | ||
Event_Enable | π | ||
Acked_Transitions | π | ||
Notify_Type | π | ||
Event_Time_Stamps | π | ||
Profile_Name | π· | R |
Analog Value
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | π· | R | |
Object_Name | π· | R | |
Object_Type | π· | R | |
Present_Value | π· | W | |
Description | π· | R | |
Status_Flags | π· | R | |
Event_State | π· | R | |
Reliability | π· | R | |
Out_Of_Service | π· | R | |
Units | π· | R | |
Priority_Array | π | ||
Relinquish_Default | π | ||
COV_Increment | π | ||
Time_Delay | π | ||
Notification_Class | π | ||
High_Limit | π | ||
Low_Limit | π | ||
Deadband | π | ||
Limit_Enable | π | ||
Event_Enable | π | ||
Acked_Transitions | π | ||
Notify_Type | π | ||
Event_Time_Stamps | π | ||
Profile_Name | π· | R |
Binary Input
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | π· | R | |
Object_Name | π· | R | |
Object_Type | π· | R | |
Present_Value | π· | R | |
Description | π· | R | |
Device_Type | π· | R | |
Status_Flags | π· | R | |
Event_State | π· | R | |
Reliability | π· | R | |
Out_Of_Service | π· | W | |
Polarity | π· | R | |
Inactive_Text | π· | R | |
Active_Text | π· | R | |
Change_Of_State_Time | π | ||
Change_Of_State_Count | π | ||
Time_Of_State_Count_Reset | π | ||
Elapsed_Active_Time | π | ||
Time_Of_Active_Time_Reset | π | ||
Time_Delay | π | ||
Notification_Class | π | ||
Alarm_Value | π | ||
Event_Enable | π | ||
Acked_Transitions | π | ||
Notify_Type | π | ||
Event_Time_Stamps | π | ||
Profile_Name | π· | R |
Binary Value
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | π· | R | |
Object_Name | π· | R | |
Object_Type | π· | R | |
Present_Value | π· | W | |
Description | π· | R | |
Status_Flags | π· | R | |
Event_State | π· | R | |
Reliability | π· | R | |
Out_Of_Service | π· | R | |
Inactive_Text | π· | R | |
Active_Text | π· | R | |
Change_Of_State_Time | π | ||
Change_Of_State_Count | π | ||
Time_Of_State_Count_Reset | π | ||
Elapsed_Active_Time | π | ||
Time_Of_Active_Time_Reset | π | ||
Minimum_Off_Time | π | ||
Minimum_On_Time | π | ||
Priority_Array | π | ||
Relinquish_Default | π | ||
Time_Delay | π | ||
Notification_Class | π | ||
Alarm_Value | π | ||
Event_Enable | π | ||
Acked_Transitions | π | ||
Notify_Type | π | ||
Event_Time_Stamps | π | ||
Profile_Name | π· | R |
Device
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | π· | W | |
Object_Name | π· | W | |
Object_Type | π· | R | |
System_Status | π· | R | |
Vendor_Name | π· | R | |
Vendor_Identifier | π· | R | |
Model_Name | π· | R | |
Firmware_Revision | π· | R | |
Application_Software_Version | π· | R | |
Location | π· | R | |
Description | π· | R | |
Protocol_Version | π· | R | |
Protocol_Revision | π· | R | |
Protocol_Services_Supported | π· | R | |
Protocol_Object_Types_Supported | π· | R | |
Object_List | π· | R | |
Structured_Object_List | π | ||
Max_APDU_Length_Accepted | π· | R | |
Segmentation_Supported | π· | R | |
Max_Segments_Accepted | π· | R | |
VT_Classes_Supported | π | ||
Active_VT_Sessions | π | ||
Local_Time | π | ||
Local_Date | π | ||
UTC_Offset | π | ||
Daylight_Savings_Status | π | ||
APDU_Segment_Timeout | π· | R | |
APDU_Timeout | π· | R | |
Number_Of_APDU_Retries | π· | R | |
List_Of_Session_Keys | π | ||
Time_Synchronization_Recipients | π | ||
Max_Master | π· | R | |
Max_Info_Frames | π· | R | |
Device_Address_Binding | π· | R | |
Database_Revision | π· | R | |
Configuration_Files | π | ||
Last_Restore_Time | π | ||
Backup_Failure_Timeout | π | ||
Backup_Preparation_Time | π | ||
Restore_Preparation_Time | π | ||
Restore_Completion_Time | π | ||
Backup_And_Restore_State | π | ||
Active_COV_Subscriptions | π· | R | |
Slave_Proxy_Enable | π | ||
Manual_Slave_Adress_Binding | π | ||
Auto_Slave_Discovery | π | ||
Slave_Address_Binding | π | ||
Last_Restart_Reason | π | ||
Time_Of_Device_Restart | π | ||
Restart_Notification_Recipients | π | ||
UTC_Time_Synchronization_Recipients | π | ||
Time_Synchronization_Interval | π | ||
Align_Intervals | π | ||
Interval_Offset | π | ||
Serial_Number (Proprietary) | π· | R | |
Profile_Name | π· | R |
Multistate Input
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | π· | R | |
Object_Name | π· | R | |
Object_Type | π· | R | |
Present_Value | π· | R | |
Description | π· | R | |
Status_Flags | π· | R | |
Event_State | π· | R | |
Reliability | π· | R | |
Out_Of_Service | π· | W | |
Number_Of_States | π· | R | |
State_Text | π· | R | |
Time_Delay | π | ||
Notification_Class | π | ||
Alarm_Values | π | ||
Fault_Values | π | ||
Event_Enable | π | ||
Acked_Transitions | π | ||
Notify_Type | π | ||
Event_Time_Stamp | π | ||
Event_Message_Texts | π | ||
Profile_Name | π· | R |
Multistate Value
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | π· | R | |
Object_Name | π· | R | |
Object_Type | π· | R | |
Present_Value | π· | W | |
Description | π· | R | |
Status_Flags | π· | R | |
Event_State | π· | R | |
Reliability | π· | R | |
Out_Of_Service | π· | R | |
Number_Of_States | π· | R | |
State_Text | π· | R | |
Priority_Array | π | ||
Relinquish_Default | π | ||
Time_Delay | π | ||
Notification_Class | π | ||
Alarm_Values | π | ||
Fault_Values | π | ||
Event_Enable | π | ||
Acked_Transitions | π | ||
Notify_Type | π | ||
Event_Time_Stamps | π | ||
Profile_Name | π· | R |
Positive Integer Value
Properties | supported | Readable/ Writable |
Range restrictions |
---|---|---|---|
Object_Identifier | π· | R | |
Object_Name | π· | R | |
Object_Type | π· | R | |
Description | π· | R | |
Present_Value | π· | W | |
Status_Flags | π· | R | |
Event_State | π· | R | |
Reliability | π· | R | |
Out_Of_Service | π· | R | |
Units | π· | R | |
Priority_Array | π | ||
Relinquish_Default | π | ||
COV_Increment | π | ||
Time_Delay | π | ||
Notification_Class | π | ||
High_Limit | π | ||
Low_Limit | π | ||
Deadband | π | ||
Limit_Enable | π | ||
Event_Enable | π | ||
Acked_Transitions | π | ||
Notify_Type | π | ||
Event_Time_Stamps | π | ||
Profile_Name | π· | R |